Chapter 4 Parameter Index
82
Pb: MODBUS communication
Functi
on
code
Parameter name
LCD display
Setting range
Factory
setting
Mo
difi
cati
on
MOD
BUS
addres
s
Pb.00
Baud rate
selection
Baud rate
selection
0: 1200bps
1: 2400bps
2: 4800bps
3: 9600 bps
4: 19200bps 5: 38400bps
3
×
0C00
Pb.01
Local address
Local address
0~31
1
×
0C01
Pb.02
Even-odd check
selection
Check bit
selection
0: Even parity
1: Odd parity
2: No parity
0
×
0C02
Pb.03
Communication
timeout
detection time
Communication
timeout
detection
Time
0.0~100.0s
0: No timeout detection
Other: Timeout detection
time
0.0s
○
0C03
Pb.04
Response delay
time
Response delay
0~500ms
5ms
×
0C04
Pb.05
Communication
transmission
frequency
command unit
Frequency
command unit
0: 0.01Hz
1: 0.1Hz
0
×
0C05
Pb.06
Communication
data Eeprom
save options
Communication
data Eeprom
save options
0: Not save Eeprom directly
1: Save Eeprom directly
0
×
0C06
Pb.07
CCF6
Troubleshooting
CCF6
Troubleshooting
0: Resume without reporting
failure
1: Reported failure and shut
down automatically
0
×
0C07
Pb.08
Reserve
Reserve
Reserve
0
-
0C08
PC: display control
Functi
on
code
Parameter name
LCD display
Setting range
Factor
y
setting
Mo
dif
y
MOD
BUS
addres
s
PC.00
LCD Language
Selection
Language
Selection
0: Chinese 1: English
0
○
0D00
PC.01
Output
frequency (Hz)
(Before
compensation)
Output
frequency (Hz)
(Before
compensation)
0: Not displayed 1: Displayed
1
○
0D01
PC.02
Output
frequency (Hz)
(Actual)
Output
frequency (Hz)
(Actual)
0: Not displayed 1: Displayed
0
○
0D02
PC.03
Output current
(A)
Output current
(A)
0: Not displayed 1: Displayed
1
○
0D03
PC.04
Set frequency
(Hz flicker)
Set frequency
(Hz flicker)
0: Not displayed 1: Displayed
1
○
0D04
PC.05
Operating speed
(r/min)
Operating speed
(R / min)
0: Not displayed 1: Displayed
1
○
0D05