71
HM 6Split
HM 12Split
Technical data
* L 6Split: If the length of the refrigerant pipes exceeds 15 m, extra refrigerant must be added at a rate of 0.02 kg/m.
L 8Split/ L 12Split: If the length of the refrigerant pipes exceeds 15 metres, extra refrigerant must be added at a rate of
0.06 kg/m
Outdoor unit
Unit
L 6Split
L 8Split
L 12Split
Starting current
A
5
Compressor
-
Twin Rotary
Max. nominal fan performance
(heating)
m
3
/h
2 530
3 000
4 380
Fan power
W
50
86
Defrosting
-
Reverse cycle
Hot water tank drip tray
W
Integrated 110
Integrated 100
Integrated 120
High pressure critical value
MPa (bary)
-
4,15 (41,5)
Low pressure switch-off value (15 s)
MPa (bary)
-
0,079 MPa (0,79)
Height
mm
640
750
845
Width
mm
800
880 (+67 valve
cover)
970
Depth
mm
290
340 (+110 base rail)
370 (+80 base rail)
Weight
kg
46
60
74
Colour (two layers of powder coating)
-
Dark grey
Refrigerant amount
kg
1,5
2,55
2,90
Max. length of refrigerant pipe one-way
m
30*
Refrigerant pipe dimensions
-
Gas pipe:
ext. diameter 12.7 (1/2”)
Liquid line:
ext. diameter 6.35 (1/4”)
Gas pipe: ext. diameter 15.88 (5/8”)
Liquid line: ext. diameter 9.53 (3/8”)
Optional pipe connections
-
Right-hand side
Bottom / right-hand
side/ back
Part no.
-
064 205
064 033
064 110
Product type
Unit
HM 6Split
HM 12Split
Height
mm
850
Required room height
mm
1 500
Width
mm
515
Depth
mm
345
Weight
kg
52
56
Maximum operating pressure of central heating system.
bar
3
Maximum operating temperature of central heating
°C
70
Maximum hot water temperature
°C
60
Low-energy circulation pump clim. sys.
-
tak
Safety valve. climate system
-
Yes, in the safety assembly
Expansion vessel
l
12
Additional heat
kW
4,5 (230V) / 9 (400V)
Rated voltage
V
230V 1N AC 50Hz / 400V 3N AC 50Hz
Energy class (in accordance with ErP. at supply temp. 55°C) applies to package
L HM 6Split, L 1 HM 12Split
-
A++
Section 13 |