59
HM 6Split
HM 12Split
Section 9 |
Control
Menu 5.5 - factory setting service
All settings can be reset (including settings available
to the user) to default values here.
IMPORTANT
When resetting, the start guide is displayed the next time
the control module is restarted with factory settings.
IMPORTANT
The signal for the AUX inputs must be a zero-voltage sig-
nal (make-break contact).
IMPORTANT
Menu 5.3.20 is inactive in the factory settings. For this
menu function to be active, installation of the accessory is
required and its activation in the accessories menu 5.2.4.
A detailed description of programming the accesso-
ries can be found in the instructions for the individual
accessories.
Menu 5.3.21 - flow sensor / energy meter
Menu 5.4 - soft in/outputs
In this menu, you can select which input on the in-
put card (AA3) can be connected to an external signal
(page 73).
Available entries on terminal strips AUX1-3 (AA3-X6:
9-14). The AUX inputs are freely programmable and
allow the introduction of additional functions using
external signals.
Input AA3-X7 is used for valve QN12 (heating / cool-
ing), hot water recirc. and alarm output.
Factory setting:
IMPORTANT
Menu 5.3.16 is inactive in the factory settings. For this
menu function to be active, you must install the accesso-
ry and activate it in the accessories menu. 5.2.4.
A detailed description of programming the accesso-
ries can be found in the instructions for the individual
accessories.
Menu 5.3.16 - humidity sensor
Menu 5.6 - forced control
Menu 5.7 - start guide
Menu 5.8 - quick start
You can force control the different components in the
control module and any connected accessories here.
This menu is used to test individual components of
the HM 6Split / HM 12Split.
The first time you start the HM 6Split / HM 12Split,
the start guide starts automatically. In this menu we
have the ability to run it manually. For more informa-
tion about the start guide, see page 42.
It is possible to start the compressor from here.
Menu 5.9 - floor drying function
length of period 1 – 7
Setting range: 0 – 30 days
Factory setting, period 1 – 3, 5 – 7: 2 days
Factory setting, period 4: 3 days
temp. period 1 – 7
Setting range: 15 – 70°C
Default value:
temp. period 1 20 °C
temp. period 2 30 °C
temp. period 3 40 °C
temp. period 4 45°C
temp. period 5 40 °C
temp. period 6 30 °C
temp. period 7 20 °C
Set the function for under floor drying here.
You can set up to seven period times with different
calculated flow temperatures. If less than seven pe-
riods are to be used, set the remaining period times
to 0 days.
Mark the active window to activate the underfloor
drying function. A counter at the bottom shows the
number of days the function has been active.
CAUTION
There must be a heating or hot water demand to start
the compressor.
CAUTION
Do not quick start the compressor too many times
over a short period of time as this may damage the
compressor and its surrounding equipment.
ADVICE
If operating mode "add. heat only" is to be
used, select it in menu 4.2.