31
HM 6Split
HM 12Split
Connecting the outdoor temperature sensor
5
4
3
2
1
SHK 200S/ SHK 200S-6
BT1
BT1
AA3-X6
The outdoor temperature sensor BT1 (included)
should be connected to the HM 6Split / HM 12Split
unit via terminal block AA3-X6:1 and AA3-X6:2.
Section 6 |
Electrical connections
Connecting the temperature sensor BT25
9
8
7
6
5
SHK 200S/ SHK 200S-6
BT25
BT25
AA3-X6
The temperature sensor BT25 (included) should be
connected to the HM 6Split / HM 12Split unit via ter-
minal block AA3-X6: 5 and AA3-X6: 6. For the location
of the sensor, see the section “Connection options”.
HM 6Split / HM12Split
HM 6Split / HM12Split
When many power consumers are connected in the
property at the same time as the electric additional
heat is in operation, there is a risk of the property’s
main fuses tripping. Control module has an integrat-
ed load monitor that controls the power steps for the
electric additional heat by disconnecting step by step
in event of overload in a phase. Reconnection occurs
when other current consumption is reduced.
A current sensor (BE1 - BE3) must be installed on
each incoming phase conductor into the electrical
distribution unit, to measure the current. The electri-
cal distribution unit is an appropriate installation point.
Connect the current sensors to a multi-core cable in
an enclosure next to the electrical distribution unit.
Use unscreened multi-core cable of at least 0.5 mm²,
from the enclosure to control module.
Connect the cable to the input board (AA3) on termi-
nal block X4:1-4 where X4:1 is the common terminal
block for the three current sensors.
The value for the size of the fuse is set in menu 5.1.12
to correspond with the size of the property’s main
fuse. Here it is also possible to adjust the current
sensor’s transformer ratio. Enclosed current sensors
have a transformer ratio of 300 and, if these are used,
the incoming current must not exceed 50 A.
LOAD MONITOR
Connecting current sensors
CAUTION
The voltage from the current sensor to the input
board must not exceed 3.2 V.
1
2
3
4
5
6
SMO
E
xternt
E
xternal
Control module
BE3
BE2
BE1
AA3
-
X4
AA3
-
X4
N
E
P
L
1
L
2
L
3
Electrical distribution
unit
Control module
Incoming electricity
LEK
Connecting the temperature sensor BT6
Connecting the temperature sensor BT7
11
10
9
8
7
SHK 200S/ SHK 200S-6
BT6
BT6
AA3-X6
18
17
16
15
SHK 200S/ SHK 200S-6
BT7
BT7
AA3-X6
The temperature sensor BT6 (included) should be
connected to the HM 6Split / HM 12Split unit via ter-
minal block AA3-X6: 7 and AA3-X6: 8.
The temperature sensor BT7 (included) should be
connected to the HM 6Split / HM 12Split unit via ter-
minal block AA3-X6: 15 and AA3-X6: 16.
NOTE
The location of the other sensors is available on
page 80.
HM 6Split / HM12Split
HM 6Split / HM12Split
If the current value is set too low, it may turn off the
electric heater / heaters and reduce the heat pump’s
power.