Rockwell Automation Publication 1756-UM010C-EN-P - June 2021
93
Chapter 5 Configure the Configurable Flowmeter Module
C.Operations[0].kFactStruct.kFactorForChan[5]
Float
REAL
This tag is an ordered pair with tag
C.Operations[0].kFactStruct.FreqAtKFactor [5]
0.0
C.Operations[0].kFactStruct.kFactorForChan[6]
Float
REAL
This tag is an ordered pair with tag
C.Operations[0].kFactStruct.FreqAtKFactor [6]
0.0
C.Operations[0].kFactStruct.kFactorForChan[7]
Float
REAL
This tag is an ordered pair with tag
C.Operations[0].kFactStruct.FreqAtKFactor [7]
0.0
C.Operations[0].kFactStruct.kFactorForChan[8]
Float
REAL
This tag is an ordered pair with tag
C.Operations[0].kFactStruct.FreqAtKFactor [8]
0.0
C.Operations[0].kFactStruct.kFactorForChan[9]
Float
REAL
This tag is an ordered pair with tag
C.Operations[0].kFactStruct.FreqAtKFactor [9]
0.0
C.Operations[0].kFactStruct.kFactorForChan[10]
Float
REAL
This tag is an ordered pair with tag
C.Operations[0].kFactStruct.FreqAtKFactor [10]
0.0
C.Operations[0].kFactStruct.kFactorForChan[11]
Float
REAL
This tag is an ordered pair with tag
C.Operations[0].kFactStruct.FreqAtKFactor [11]
0.0
C.Operations[0].kFactStruct.kFactorForChan[12]
Float
REAL
This tag is an ordered pair with tag
C.Operations[0].kFactStruct.FreqAtKFactor [12]
0.0
C.Operations[0].kFactStruct.FreqAtKFactor[0]
Float
REAL
100.0
C.Operations[0].kFactStruct.FreqAtKFactor[1]
Float
REAL
Freq[1] for KFactor [1]
0.0
C.Operations[0].kFactStruct.FreqAtKFactor[2]
Float
REAL
Freq[2] for KFactor [2]
500.0
C.Operations[0].kFactStruct.FreqAtKFactor[3]
Float
REAL
Freq[3] for KFactor [3]
0.0
C.Operations[0].kFactStruct.FreqAtKFactor[4]
Float
REAL
Freq[4] for KFactor [4]
0.0
C.Operations[0].kFactStruct.FreqAtKFactor[5]
Float
REAL
Freq[5] for KFactor [5]
0.0
C.Operations[0].kFactStruct.FreqAtKFactor[6]
Float
REAL
Freq[6] for KFactor [6]
0.0
C.Operations[0].kFactStruct.FreqAtKFactor[7]
Float
REAL
Freq[7] for KFactor [7]
0.0
C.Operations[0].kFactStruct.FreqAtKFactor[8]
Float
REAL
Freq[8] for KFactor [8]
0.0
C.Operations[0].kFactStruct.FreqAtKFactor[9]
Float
REAL
Freq[9] for KFactor [9]
0.0
C.Operations[0].kFactStruct.FreqAtKFactor[10]
Float
REAL
Freq[10] for KFactor [10]
0.0
C.Operations[0].kFactStruct.FreqAtKFactor[11]
Float
REAL
Freq[11] for KFactor [11]
0.0
C.Operations[0].kFactStruct.FreqAtKFactor[12]
Float
REAL
Freq[12] for KFactor [12]
0.0
C.OutputSetup[0].FaultMode
Decimal
SINT
Sets the state of output 0 when communications are lost
with the owner-controller in Fault Mode
0 = Continue operation
1 = Reset Output 0 to OFF when in Fault Mode
2 = Set Output 0 to ON when in Fault Mode
1
C.OutputSetup[0].ProgMode
Decimal
SINT
Sets the state of output 0 when communications are lost
with the owner-controller in Program Mode
0 = Continue operation
1 = Reset Output 0 to OFF when in Program Mode
2 = Set Output 0 to ON when in Program Mode
0
C.OutputSetup[0].DynamicError
Decimal
SINT
Sets the state of output 0 when a dynamic error occurs
0 = Continue operation
1 = Reset Output 0 to OFF on Error
2 = Set Output 0 to ON on Error
0
C.OutputSetup[0].TriggerOn
Decimal
SINT
Sets when output 0 energizes
0 = No Action
1 = Frequency
2 = Acceleration
3 = Full Flow State (N/A in this mode)
4 = Trickle Flow State (N/A in this mode)
5 = Prover Run State
6 = Prover Range State
0
Table 8 - Tag Changes Required for Totalizer Mode Using Prover Function
Name
Style
Data Type
Definition
Enter This
Value