110
Rockwell Automation Publication 1756-UM010C-EN-P - June 2021
Appendix B Software Configuration Tags
C.Operations[1].FillMode
Decimal
SINT
Sets the Trickle mode for engineering units or time.
0 = Engineering units
1 = Time
C.Operations[1].MinDetectableFreq
Float
REAL
User-defined value from 0 - 100,000.
Sets FreqAverage, FreqPeriod, Speed, GrossRate, and NetRate reading to 0
when calculated value is less than value entered. GrossVolume, and
NetVolume do not increment below this value even though TotalCounts
increments over time.
C.Operations[1].HighestAllowedFreq
Float
REAL
User-defined value between MinDetectableFreq and 120,000
When the frequency reaches this level, it sets the Overflow alarm limit
C.Operations[1].AccelAlarmValue
Float
REAL
Sets Acceleration alarm limit
-Maximum acceleration (cycles per second
2
) <AccelAlarmValue<
+Maximum acceleration (cycles per second
2
)
C.Operations[1].MeterFactor
Float
REAL
Calibration Adjust for metering reading applied after K-factor correction.
Typically, this factor is between 0.8 and 1.2 but the module restricts the
value>0.
C.Operations[1].FilterResolution
Float
REAL
Sets resolution of the Speed calculation based on the raw counts
0 = default of 0.00001
0.00001 = resolution of + 1 count of 100,000 raw counts.
C.Operations[1].SampleTime
Float
REAL
Sets time for a sample to be taken.
0 - 5.0 seconds (2.0 second maximum sample time for High Resolution
mode)
C.Operations[1].kFactStruct.kFactorForChan[0]
Float
REAL
K-factor 0 for Channel 1 when frequency is < FreqAtKFactor[1]
C.Operations[1].kFactStruct.kFactorForChan[1]
Float
REAL
This tag is an ordered pair with tag
C.Operations[1].kFactStruct.FreqAtKFactor [1]
C.Operations[1].kFactStruct.kFactorForChan[2]
Float
REAL
This tag is an ordered pair with tag
C.Operations[1].kFactStruct.FreqAtKFactor [2]
C.Operations[1].kFactStruct.kFactorForChan[3]
Float
REAL
This tag is an ordered pair with tag
C.Operations[1].kFactStruct.FreqAtKFactor [3]
C.Operations[1].kFactStruct.kFactorForChan[4]
Float
REAL
This tag is an ordered pair with tag
C.Operations[1].kFactStruct.FreqAtKFactor [4]
C.Operations[1].kFactStruct.kFactorForChan[5]
Float
REAL
This tag is an ordered pair with tag
C.Operations[1].kFactStruct.FreqAtKFactor [5]
C.Operations[1].kFactStruct.kFactorForChan[6]
Float
REAL
This tag is an ordered pair with tag
C.Operations[1].kFactStruct.FreqAtKFactor [6]
C.Operations[1].kFactStruct.kFactorForChan[7]
Float
REAL
This tag is an ordered pair with tag
C.Operations[1].kFactStruct.FreqAtKFactor [7]
C.Operations[1].kFactStruct.kFactorForChan[8]
Float
REAL
This tag is an ordered pair with tag
C.Operations[1].kFactStruct.FreqAtKFactor [8]
C.Operations[1].kFactStruct.kFactorForChan[9]
Float
REAL
This tag is an ordered pair with tag
C.Operations[1].kFactStruct.FreqAtKFactor [9]
C.Operations[1].kFactStruct.kFactorForChan[10]
Float
REAL
This tag is an ordered pair with tag
C.Operations[1].kFactStruct.FreqAtKFactor [10]
C.Operations[1].kFactStruct.kFactorForChan[11]
Float
REAL
This tag is an ordered pair with tag
C.Operations[1].kFactStruct.FreqAtKFactor [11]
C.Operations[1].kFactStruct.kFactorForChan[12]
Float
REAL
This tag is an ordered pair with tag
C.Operations[1].kFactStruct.FreqAtKFactor [12]
C.Operations[1].kFactStruct.FreqAtKFactor[0]
Float
REAL
C.Operations[1].kFactStruct.FreqAtKFactor[1]
Float
REAL
Freq[1] for KFactor [1]
C.Operations[1].kFactStruct.FreqAtKFactor[2]
Float
REAL
Freq[2] for KFactor [2]
C.Operations[1].kFactStruct.FreqAtKFactor[3]
Float
REAL
Freq[3] for KFactor [3]
C.Operations[1].kFactStruct.FreqAtKFactor[4]
Float
REAL
Freq[4] for KFactor [4]
C.Operations[1].kFactStruct.FreqAtKFactor[5]
Float
REAL
Freq[5] for KFactor [5]
Table 14 - Configurable Flowmeter Module Configuration Tags
Name
Style
Data Type
Definition