76
Rockwell Automation Publication 1756-UM010C-EN-P - June 2021
Chapter 5 Configure the Configurable Flowmeter Module
Altering the Default
Configuration
If you want to alter or view the default configuration, click Next. On the next
wizard screen, you can change the module’s configuration as shown.
After you finish the Module Properties screen, you must access the module
tags, via the Tag Editor, to make additional configuration changes, see
If you want a
Major Fault on the Controller
to
occur if there is connection failure with the I/O
module, click here
This Fault box is empty when you are
offline. If a fault occurs while the module
is online, the type of fault will be
displayed here
Inhibit
the connection to the module here
Adjust the
Requested Packet Interval
here.
Click here to finish this portion of configuration and
move to the Tag Editor, see
.
IMPORTANT
: Minimum RPI values:
• 50 ms for one channel in Totalizer mode
• 100 ms for two channels in Totalizer mode
• 5 ms for one channel in High Resolution
Frequency mode
• 10 ms for two channels in High Resolution
Frequency mode
• 55 ms for one channel in each mode
IMPORTANT
Two additional wizard screens appear during initial module
configuration. The screens are used during online application monitoring
but are shown below to give you an accurate description of the screens
that appear during initial configuration.