Chapter 5 Configure the Configurable Flowmeter Module
3. Access the module tags via the Tag Editor, see
4. Change
only
the tags listed in
. You can ignore all other tags; they
do not affect High Resolution Frequency mode
Table 7 - Tag Changes Required for High Resolution Frequency Mode
Name
Style
Data Type
Definition
Enter This
Value
C.Ch0LowFreqClear
Decimal
BOOL
Enables the minimum detectable frequency level for Channel 0.
Set the bit to 1 to enable it
1
C.Operations[0].OperationalMode
Decimal
SINT
Sets the module’s operational mode.
0 = OFF
1 = Totalizer Mode
2 = Non-Resettable Totalizer Mode
3 = High Resolution Frequency Mode
3
C.Operations[1].OperationalMode
Decimal
SINT
Sets the module’s operational mode.
0 = OFF
1 = Totalizer Mode
2 = Non-Resettable Totalizer Mode
3 = High Resolution Frequency Mode
0
C.Operations[0].AccelCalculation
Decimal
SINT
Number of past samples to use to calculate an acceleration value.
Sample range is 0 to 255.
50
C.Operations[0].MeterFactor
Float
REAL
Calibration Adjust for metering reading applied after K-factor
correction. Typically, this factor is between 0.8 and 1.2 but the
module restricts the value>0.
0
C.Operations[0].FilterResolution
Float
REAL
Sets resolution of the Speed calculation based on the raw counts
0 = default of 0.00001
0.00001 = resolution of + 1 count of 100,000 raw counts.
0.00001
C.Operations[0].SampleTime
Float
REAL
Sets time for a sample to be taken.
(2.0 second maximum sample time for High Resolution Frequency
mode and 5.0 second maximum sample time for Totalizer mode)
0.033
C.Operations[0].HighestAllowedFreq
Float
REAL
User-defined value between MinDetectableFreq and 120,000
When the frequency reaches this level, it sets the Overspeed alarm
limit
3700
C.Operations[0].AccelAlarmValue
Float
REAL
Sets Acceleration alarm limit
-Maximum acceleration (cycles per second
2
) <AccelAlarmValue<
+Maximum acceleration (cycles per second
2
)
100
C.OutputSetup[0].TriggerOn
Decimal
SINT
Sets when output 0 energizes
0 = No Action
1 = Frequency
2 = Acceleration
3 = Full Flow State (N/A in this mode)
4 = Trickle Flow State (N/A in this mode)
5 = Prover Run State (N/A in this mode)
6 = Prover Range State (N/A in this mode)
0
C.OutputSetup[0].TieToCounter
Ties a channel to output 0
0 = No connection
1 = Connect Channel0 to Output0
2 = Connect Channel1 to Ouput0
0
O.Total[0].CombinedCorrectionFactor
Float
REAL
0 = Default value of 1.0
Use this value to convert from Hz to RPMs. Results are displayed in
Frequency Average only
60
O.Total[0].Overrange
Decimal
BOOL
Enables the Overrange alarm on output connected to channel 1.
When the Frequency Average exceeds 100KHz, this alarm is set.
0 = No Alarm
1 = Alarm Enabled
0
O.Total[0].Overspeed
Decimal
BOOL
Enables the Overspeed alarm on output connected to channel 0.
When the Speed exceeds the Highest Allowed Frequency value, this
alarm is set.
0 = No Alarm
1 = Alarm Enabled
1