Publication 0160-5.18 - June 2003
6-30
Using 160-DN2 with DeviceNet Scanner
Using Explicit Messaging
(Continued)
ControlLogix Example
Data Format for a Read and Write Parameter
The data in this example is for a Bulletin 160-SSC drive at MAC ID
1.
For a description of the content in each box, refer to the “
Figure 6.21
ParameterReadMessage Screen
Box
Setting
Description
Refer to . . .
Message Type
Service Type
Class
Instance
Attribute
Destination
CIP Generic
Get Attribute Single
B3 (hex)
1 (dec)
3 (hex)
➁
Must be CIP Generic
Defines Service Code as text message
160 Parameter Table Object
Number of Instances
Parameter Number
➀
User-created tag for parameter data
➀
For this example screen, Parameter 3 - [Output Current] was selected.
➁
For this example screen, the tag Output_Current was created and assigned. To create a
tag, click
New Tag
, enter tag name, select Data Type, and click
OK
. To assign this tag,
click on the Destination dropdown arrow, select the defined tag, and click outside the
dropdown list.