Publication 0160-5.18 - June 2003
B-22
DeviceNet Information
Class Code 0xB4 —
DN Interface Object
Instance 1 Attributes
➀
If set to a “9,”
P9 - [Drive Status]
(of the SSC Interface Profile) goes in the low byte of the assembly field, and
P12 - [Input Status]
(of the SSC Interface
Profile) goes in the high byte of the assembly field.
Common Services
Class Attributes:
None Supported
Number of Instances:
1
Attribute ID
Access
Rule
Name
Data
Type
Min/Max
Default
Description
1
Get
Zero
USINT
0
0
Returns zero.
2
Get
Interface Select USINT
0
0
0 =
Bulletin 160 SSC Interface
.
3 Get
MAC ID
Switches
USINT
0 to 63
Reflects the state of the MAC ID switches.
4
Get
Baud Switches
USINT
0 to 3
Reflects the state of the Baud Rate switches.
5 Get/Set
Nonvolatile MAC
ID
USINT
0 to 63
63
Stored value of the MAC ID. This value is used when Baud
Rate Switches 7 and 8 are ON.
6
Get/Set
Nonvolatile Baud USINT
0 to 2
0
Stored value of Baud Rate. This value is used when Baud
Rate Switches 7 and 8 are ON.
7
➀
Get/Set
Assembly
Word 0 Param
USINT
0 to 88
9
Bulletin 160 SSC Interface
parameter number whose value is
used as the first word in Input Assembly 102.
8
➀
Get/Set
Assembly
Word 1 Param
USINT
0 to 88
0
Bulletin 160 SSC Interface
parameter number whose value is
used as the second word in Input Assembly 102.
9
➀
Get/Set
Assembly
Word 2 Param
USINT
0 to 88
0
Bulletin 160 SSC Interface
parameter number whose value is
used as the third word in Input Assembly 102.
10
➀
Get/Set
Assembly
Word 3 Param
USINT
0 to 88
0
Bulletin 160 SSC Interface
parameter number whose value is
used as the fourth word in Input Assembly 102.
11
Get/Set
DN Idle Mode
BOOL
0 to 1
0
0 = Stop, 1 = Hold Last State.
12
Get
DN Software
Version
WORD
0.00 to 10.00
2.00
Indicates the software version of the DeviceNet option.
13
Get/Set
DN Change of
State Mask
WORD
0 to 0xFFFF
0xFFFF
A 16 bit mask used to enable automatic change of state
messages.
14
Get/Set
Local Return
Mode
BYTE
0 to 5
0
Sets the input mode the drive will use when transitioning from
network to local control.
15
Get
DeviceNet DIP
Switches
BYTE
0 to 255
Current DIP switch settings on the 160-DN2 module.
Service
Code
Implemented for:
Service
Name
Class
Instance
0x0E
No
Yes
Get_Attribute_Single
0x10
No
Yes
Set_Attribute_Single
Summary of Contents for 160-DN2
Page 1: ...User Manual DeviceNet Communication Module Catalog Number 160 DN2 Firmware 3 xxx...
Page 8: ...iv Table of Contents Publication 0160 5 18 June 2003...
Page 80: ...Publication 0160 5 18 June 2003 7 6 Troubleshooting Notes...
Page 82: ...Publication 0160 5 18 June 2003 A 2 Specifications Notes...
Page 115: ......