Publication 0160-5.18 - June 2003
Chapter
4
Modes of Operation
This chapter contains information about:
• Powering up the drive with an installed 160-DN2 DeviceNet
communication module.
• Understanding the module’s modes of operation.
Before you apply power, review the
on Preface
Powering Up the Drive
After you have installed the 160-DN2 module, apply power to the
drive and to the Network. The COMM LED should flash green or turn
solid green. If it does not, refer to
Modes of Operation
The 160-DN2 module operating modes are:
• Power-up reset mode
• Run mode
• Error mode
Power-up Reset Mode
During power-up or reset, the COMM LED is off.
The 160-DN2 module follows this sequence of operation:
1.
When power-up occurs, the COMM LED flashes green for 1/4
second, red for 1/4 second, and then goes blank while the 160-
DN2 module finishes its initialization.
2.
Performs power-up initialization.
3.
Reads and stores the DIP switch settings.
4.
Performs a duplicate node address check to verify that another
node is not assigned the same DeviceNet address as the 160-DN2
module.
If the power-up or reset is successful, the 160-DN2 module enters the
Run mode and the COMM LED flashes green or turns solid green.
Summary of Contents for 160-DN2
Page 1: ...User Manual DeviceNet Communication Module Catalog Number 160 DN2 Firmware 3 xxx...
Page 8: ...iv Table of Contents Publication 0160 5 18 June 2003...
Page 80: ...Publication 0160 5 18 June 2003 7 6 Troubleshooting Notes...
Page 82: ...Publication 0160 5 18 June 2003 A 2 Specifications Notes...
Page 115: ......