Publication 0160-5.18 - June 2003
6-26
Using 160-DN2 with DeviceNet Scanner
Using Explicit Messaging
(Continued)
Explicit Messages for a PLC-5 or SLC Controller
Transaction blocks in PLC-5 and SLC scanners accommodate both
downloading Explicit Message Requests and uploading Explicit
Message Responses. The scanner module can accommodate one
request or response for each transaction block. Each transaction block
must be formatted as shown in
Figure 6.18
PLC-5 Explicit Message Format
Figure 6.19
SLC Explicit Message Format
for a description of the data that is
required in each word.
The following table identifies the number of transaction blocks within
a scanner that are reserved for Explicit Messaging.
Bit
15
0
15
0
Word 0
TXID
Command
TXID
Status
Port
Size
Port
Size
Service
Address
Service
Address
Class
Service Response Data
Instance
Attribute
Word 6 - 31 Service Data
Word 32
TXID
Command
TXID
Status
Port
Size
Port
Size
Service
Address
Service
Address
Class
Service Response Data
Instance
Attribute
Word 38 -
63
Service Data
Bit
15
0
15
0
Word 0
TXID
Command
TXID
Status
Port
Size
Port
Size
Service
Address
Service
Address
Class
Service Response Data
Instance
Attribute
Word 6 - 31 Service Data
Scanner
Number of
Transaction Blocks
Words in Each
Transaction Block
Refer to . . .
1771-SDN
10
32 (two blocks can be moved at once)
1747-SDN
10
32
Request
Response
Request
Response
Summary of Contents for 160-DN2
Page 1: ...User Manual DeviceNet Communication Module Catalog Number 160 DN2 Firmware 3 xxx...
Page 8: ...iv Table of Contents Publication 0160 5 18 June 2003...
Page 80: ...Publication 0160 5 18 June 2003 7 6 Troubleshooting Notes...
Page 82: ...Publication 0160 5 18 June 2003 A 2 Specifications Notes...
Page 115: ......