Setting the Baud Rate
Dip switches 7 and 8 set the baud rate at which the Communication
Module communicates on the network. The factory default setting for
baud rate is 125 kbps.
Figure 3.7
Setting the Baud Rate
To set the DeviceNet Baud Rate:
1.
for the switch setting of a specific Baud Rate.
2.
Slide switches 7 and 8 to the appropriate positions using a pointed
tool.
Important:
When switches 7 and 8 are ON, the DeviceNet Baud
Rate is set to the value in parameter
P104 - [NV Baud Rate].
Cable Lengths and Baud Rates
The baud rate determines the maximum length of the DeviceNet
cable. Refer to
to determine cable lengths and baud rates.
1
2
3
4
5
6
7
8
O
N
ON = 1
OFF = 0
Use DIP Switch 8 and 7 for
setting the DeviceNet Baud
Rate.
Table 3.B Switch Settings for DeviceNet Module Baud Rate
Baud Rate
Switch Setting
8
Switch Setting
7
125 kbps
0
0
250 kbps
0
1
500 kbps
1
0
Set by module parameter P104
1
1
Table 3.C Baud Rate vs. Cable Length
Baud Rate
Maximum Cable Length
(Trunk Line)
125 kbps
500 meters (1640 feet)
250 kbps
250 meters (820 feet)
500 kbps
100 meters (328 feet)