Publication 0160-5.18 - June 2003
Using 160-DN2 with DeviceNet Scanner
6-17
Using I/O Messaging (Continued)
ControlLogix Example
Figure 6.14
Example ControlLogix Ladder Logic Program
Table 6.C Tags for the Example Program
Tag Name
Type
Tag Name
Type
Local:1:I
DINT[]
DriveFeedback
INT
Local:1:O
DINT[]
DriveInputImage
INT[2]
DriveCommandClearFault
BOOL
DriveOutputImage
INT[2]
DriveCommandJog
BOOL
DriveReference
INT
DriveCommandStart
BOOL
DriveStatusFaulted
BOOL
DriveCommandStop
BOOL
DriveStatusRunning
BOOL
0
Local:1:O.CommandRegister.Run
1
Copy File
Source Local:1:I.Data[0]
Dest DriveInputImage[0]
Length
2
COP
2
DriveInputImage[0].1
DriveStatusRunning
3
DriveInputImage[0].7
DriveStatusFaulted
4
Copy File
Source DriveInputImage[1]
Dest
DriveFeedback
Length
1
COP
5
DriveCommandStart
DriveOutputImage[0].1
6
DriveCommandStop
DriveOutputImage[0].0
7
DriveCommandJog
DriveOutputImage[0].2
This rung enables the DeviceNet scanner.
This rung copies the 32-bit DeviceNet scanner input image into
an array of two 16-bit words. The length in this instruction is two
because two 16-bit array elements of the destination are used.
These rungs read the Running and Faulted status bits from the
input image of the drive and place the data in respective tags.
This rung reads the drive’s Feedback word and places it in
the Feedback tag.
These rungs move the inputs of the operator from the
operator station to the drive’s output image.
Summary of Contents for 160-DN2
Page 1: ...User Manual DeviceNet Communication Module Catalog Number 160 DN2 Firmware 3 xxx...
Page 8: ...iv Table of Contents Publication 0160 5 18 June 2003...
Page 80: ...Publication 0160 5 18 June 2003 7 6 Troubleshooting Notes...
Page 82: ...Publication 0160 5 18 June 2003 A 2 Specifications Notes...
Page 115: ......