Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
491
CIP Objects
Appendix A
Dynamix MUX Object
The MUX Object (class code 0x39B) defines and controls the multiplexing
capability of the main module that is based on single or multiple
configurations. Up to three subchannels can be configured each based on one
DSP stored configuration and each having up to four time slots for which
measurement channels can be enabled in either single or parallel mode. This is
as long as the DSP can process each configuration option
Main setup for multiplexing operation using single configuration or multi-
parameter mode is under high-level configuration control. This determines the
number of subchannels and the allocation of channels to time slots. Settling
and Data Acquisition times for the time slots are automatically set at minimum
acceptable values that take account of signal processing requirements.
Table 237 - Object Instances
Instance ID
Description
0
MUX Class Instance
1
Instances 1 for subchannel A MUX configuration
Table 238 - Class Attributes
Attribute
ID
Access
Rule
NV
Name
Data
Type
Description of
Attribute
Semantics of
Values
1
Get
NV
Revision
UINT
Current object revision.
Current revision.
8
Get
V
MUX Configured
BOOL
Whether this
configuration uses MUX.
9
Get
V
Number of Enabled
Subchannels
USINT
Enabled subchannels/
instances.
1
16
Get
V
Overall Cycle Time
REAL
Time that is taken to
complete a MUX cycle.
Table 239 - Instance Attributes
Attribute
ID
Access
Rule
NV
Name
Data Type
Description of
Attribute
Semantics of
Values
Read Time Slot Configuration
Group of 9 configuration attributes.
1
Get
V
Time Slot Channel
Enables
WORD
Bit-wise channel
enables for time slots
1…3.
All 16 bits
used
2
Get
V
Time Slot 0 DAQ
Time
REAL
Time Slot 0 DAQ Time
s
3
Get
V
Time Slot 1 DAQ
Time
REAL
Time Slot 1 DAQ Time
s
4
Get
V
Time Slot 2 DAQ
Time
REAL
Time Slot 2 DAQ Time
s
5
Get
V
Time Slot 3 DAQ
Time
REAL
Time Slot 3 DAQ Time
s
6
Get
V
Time Slot 0
Settling Time
REAL
Time Slot 0 Settling
Time
s
7
Get
V
Time Slot 1
Settling Time
REAL
Time Slot 1 Settling
Time
s
8
Get
V
Time Slot 2
Settling Time
REAL
Time Slot 2 Settling
Time
s