
282
Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
Chapter 10
Operate the Module
Example 3
Table 64 - 4-Channels; Alert and Danger; Expansion Relays
Dynamic Alignment
Static Alignment
Voted Alarm 0: Actuate on Alert, Danger
Voted Alarm 0: Actuate on Danger
Voted Alarm 1: Actuate on Alert, Danger
Voted Alarm 1: Actuate on Danger
Voted Alarm 2: Actuate on Alert, Danger
Voted Alarm 2: Actuate on Danger
Voted Alarm 3: Actuate on Alert, Danger
Voted Alarm 3: Actuate on Danger
Voted Alarms 4 … 12: Not enabled
Voted Alarm 4: Actuate on Alert
Voted Alarm 5: Actuate on Alert
Voted Alarm 6: Actuate on Alert
Voted Alarm 7: Actuate on Alert
Voted Alarms 8 … 12: Not enabled
Relay 0 = Module Fault
Relay 0 = Module Fault
RELX0 Relay 0 = Voted Alarm 0, on Danger
RELX0 Relay 0 = Voted Alarm 0, on Danger
RELX0 Relay 1 = Voted Alarm 1, on Danger
RELX0 Relay 1 = Voted Alarm 1, on Danger
RELX0 Relay 2 = Voted Alarm 2, on Danger
RELX0 Relay 2 = Voted Alarm 2, on Danger
RELX0 Relay 3 = Voted Alarm 3, on Danger
RELX0 Relay 3 = Voted Alarm 3, on Danger
Relay Assigned Output; R = Reserved, NA = Not Allocated
Voted Alarm Instance
Voted Alarm Status
Alarm
Status #
0
1
2
3
Voted
Alarm#
0
1
Status to Activate
On
0
1
1
1
1
14
0
0
0
Fault
1
1
0
0
0
0
0
1
2
Danger
2
0
1
0
0
1
0
1
2
Danger
3
1
1
0
0
2
0
1
2
Danger
4
0
0
1
0
3
0
1
2
Danger
5
1
0
0
0
0
1
0
1
Alert
6
0
1
0
0
1
1
0
1
Alert
7
1
1
0
0
2
1
0
1
Alert
8
0
0
1
0
3
1
0
1
Alert
9…12
0
0
0
0
NA
0
0
0
Voted Alarm Instance
Voted Alarm Status
Alarm
Status #
0
1
2
3
Voted
Alarm#
0
1
Status to Activate
On
0
1
0
0
0
0
0
1
2
Danger
1
0
1
0
0
1
0
1
2
Danger
2
1
1
0
0
2
0
1
2
Danger
3
0
0
1
0
3
0
1
2
Danger
4
1
0
1
0
4
1
0
1
Alert
5
0
1
1
0
5
1
0
1
Alert
6
1
1
1
0
6
1
0
1
Alert
7
0
0
0
1
7
1
0
1
Alert
8 …12
0
0
0
0
NA
0
0
0