Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
487
CIP Objects
Appendix A
The Record Type Structures are as follows.
See
for details on how to calculate the FFT
from the read data.
Reference the measurement tables.
See
for details on how to calculate the TWF
from the read data.
Table 233 - FFT (eFFT)
Byte Offset
Within Structure
Structure Member
Data Type
Description
0
TimestampNanoSec
UDINT
Subsecond accuracy.
4
TimestampSec
UDINT
Seconds since 1970.
8
SamplePeriodInSecs
REAL
Time period between samples or speed and number of samples per revolution can be used to
calculate the bandwidth for the FFT.
12
Identifier
DWORD
Data source, mode, tacho source, and measurement units.
16
ucDataSelect
BYTE
If Bit 0 is set, phase array follows the mag array in the returned data array. Otherwise, just the
magnitude array is returned.
Bits 1 and 2 indicate FFT scaling: 0 Peak, 1 Peak to Peak, 2 RMS.
Bits 3 and 4 indicate the data filtering that has been applied.
Bits 5 and 6 indicate the FFT Windowing applied: 0 Normal/Rectangular, 1 Flat-Top, 2 Hanning,
3 Hamming.
17
Reserved1
BYTE
18
Reserved2
UINT
20
ByteCount
UDINT
The size of the following array in bytes.
24
LineArray
REAL
The array of FFT line amplitude data.
Table 234 - Waveform (eTWF2)
Byte Offset
Within Structure
Structure Member
Data Type
Description
0
TimestampNanoSec
UDINT
Subsecond accuracy.
4
TimestampSec
UDINT
Seconds since 1970.
8
SamplePeriodInSecs
REAL
Time period between samples or speed and number of samples per revolution.
12
Identifier
DWORD
Data source, mode, tacho source, and measurement units.
16
RelativeTime
UDINT
A 24-bit (micro-second) counter-value for finely aligning data.
See
Reading Continuous Time Waveforms on page 329
for information on using this parameter.
20
ByteCount
UDINT
The size of the following array in bytes.
24
SampleArray
REAL
The array of waveform data values (samples).