
Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
281
Operate the Module
Chapter 10
Example 2
Table 63 - 3 Channels; Alert, Danger, TX Fault; Trip on Alarm 0 Danger
Dynamic Alignment
Static Alignment
Voted Alarm 0: Actuate on Alert, Danger, TX Fault
Voted Alarm 0: Actuate on Danger
Voted Alarm 1: Actuate on Alert, Danger, TX Fault
Voted Alarm 1: Actuate on Danger
Voted Alarm 2: Actuate on Alert, Danger, TX Fault
Voted Alarm 2: Actuate on Danger
Voted Alarms 3 …12: Not enabled
Voted Alarm 3: Actuate on Alert
Voted Alarm 4: Actuate on Alert
Voted Alarm 5: Actuate on Alert
Voted Alarm 6: Actuate on TX Fault
Voted Alarm 7: Actuate on TX Fault
Voted Alarm 8: Actuate on TX Fault
Voted Alarms 9 …12: Not enabled
Relay = Voted Alarm 0, on Danger
Relay = Voted Alarm 0, on Danger
Relay Assigned Output; R = Reserved; NA = Not Allocated; TXF = Transducer Fault
Voted Alarm Instance
Voted Alarm Status
Alarm
Status #
0
1
2
3
Voted
Alarm#
0
1
Status to Activate
On
0
1
0
0
0
0
0
1
2
Danger
1
1
0
0
0
0
1
0
1
Alert
2
1
0
0
0
0
1
1
3
TXF
3
0
1
0
0
1
1
0
1
Alert
4
0
1
0
0
1
0
1
2
Danger
5
0
1
0
0
1
1
1
3
TXF
6
1
1
0
0
2
1
0
1
Alert
7
1
1
0
0
2
0
1
2
Danger
8
1
1
0
0
2
1
1
3
TXF
9…12
0
0
0
0
NA
0
0
0
Voted Alarm Instance
Voted Alarm Status
Alarm
Status #
0
1
2
3
Voted
Alarm#
0
1
Status to Activate
On
0
1
0
0
0
0
0
1
2
Danger
1
0
1
0
0
1
0
1
2
Danger
2
1
1
0
0
2
0
1
2
Danger
3
0
0
1
0
3
1
0
1
Alert
4
1
0
1
0
4
1
0
1
Alert
5
0
1
1
0
5
1
0
1
Alert
6
1
1
1
0
6
1
1
3
TXF
7
0
0
0
1
7
1
1
3
TXF
8
1
0
0
1
8
1
1
3
TXF
9 …12
0
0
0
0
NA
0
0
0