Main optical fiber installation (OC-12, OC-48, OC-192)
Equipment and cable installation for 1665 Data Multiplexer
(1665 DMX)
1 - 8 8
365-372-304R7.1
Issue 1, November 2007
............................................................................................................................................................................................................................................................
Main optical fiber installation (OC-12, OC-48, OC-192)
Description
This section describes how to route the optical fiber cables from the interconnecting
equipment (for example, a
LGX
®
optical fiber distributing frame) to the Main OLIUs of
the 1665 DMX High-Capacity shelf. This procedure does not cover routing the optical
fiber cable between sites.
The optical fiber cables will be connected to the 1665 DMX after the circuit packs are
installed. The 1665 DMX requires single-mode fiber for the main OLIUs.
Important!
The optical fiber cable is fragile and must be protected. The fibers should
be placed in a protective tube or channel, such as PVC tubing, or
PANDUIT
cable
channel, when running the cable from the 1665 DMX High-Capacity shelf to the cable
rack. The fibers should be placed in the cable rack in a protective channel with nothing
on top of them. Cable ties should NOT be used with the optical fiber cables.
Unterminated optical connectors may emit laser radiation. Do not view an unterminated
optical connector with optical instruments.
Invisible laser radiation when unterminated. Avoid direct exposure of the eyes to the
beam.
Important!
Prior to connecting the optical fiber cables, the fibers should be
examined to ensure that they are clean. See
for
recommended cleaning procedures.
WARNING
Laser hazard
WARNING
Laser hazard
Summary of Contents for Data Multiplexer Explore 1665
Page 8: ... Contents v i i i 365 372 304R7 1 Issue 1 November 2007 ...
Page 12: ... List of figures x i i 365 372 304R7 1 Issue 1 November 2007 ...
Page 16: ... List of tables x v i 365 372 304R7 1 Issue 1 November 2007 ...
Page 24: ... About this document x x i v 365 372 304R7 1 Issue 1 November 2007 ...
Page 272: ... Final operations Operational tests 5 2 2 365 372 304R7 1 Issue 1 November 2007 ...
Page 326: ... Cleaning pluggable optics modules Fiber cleaning B 1 4 365 372 304R7 1 Issue 1 November 2007 ...
Page 408: ...I N 4 365 372 304R7 1 Issue 1 November 2007 Index ...