OC-3 (LNW37, LNW45, LNW55)/OC-12 (LNW49,
LNW55)/OC-48 (LNW55, LNW62) low-speed SFP test
procedure
Installation tests
4 - 4 2
365-372-304R7.1
Issue 1, November 2007
Result:
The FAULT LED should begin flashing on the OLIU and only the MN and
NE LEDs should be lit on the SYSCTL circuit pack.
The alarm on the SFP module will flash.
........................................................................................................................................................................................................................
5
From the system view click Alarm List to verify that the circuit pack alarm is associated
with the optical port being tested.
........................................................................................................................................................................................................................
6
Select Configuration -> Update System... -> Update All.
Requirement:
The flashing FAULT LED should extinguish on the OLIU. There
should be no alarm indications on the 1665 DMX shelf.
........................................................................................................................................................................................................................
7
From the system view click Alarm List to verify that the circuit pack alarm is cleared.
........................................................................................................................................................................................................................
8
Repeat this entire procedure for each LNW37, LNW45, LNW49, LNW55 or LNW62 SFP
equipped in the 1665 DMX shelf.
........................................................................................................................................................................................................................
9
Replace all protective dust covers on the LNW37, LNW45, LNW49 or LNW62 SFP
OLIU connectors (OLIU and LGX), that were removed to perform this procedure.
........................................................................................................................................................................................................................
10
Check off the appropriate box in
Appendix E, “Installation checklist”
.
........................................................................................................................................................
E
N D
O
F
S
T E P S
Summary of Contents for Data Multiplexer Explore 1665
Page 8: ... Contents v i i i 365 372 304R7 1 Issue 1 November 2007 ...
Page 12: ... List of figures x i i 365 372 304R7 1 Issue 1 November 2007 ...
Page 16: ... List of tables x v i 365 372 304R7 1 Issue 1 November 2007 ...
Page 24: ... About this document x x i v 365 372 304R7 1 Issue 1 November 2007 ...
Page 272: ... Final operations Operational tests 5 2 2 365 372 304R7 1 Issue 1 November 2007 ...
Page 326: ... Cleaning pluggable optics modules Fiber cleaning B 1 4 365 372 304R7 1 Issue 1 November 2007 ...
Page 408: ...I N 4 365 372 304R7 1 Issue 1 November 2007 Index ...