93
X. Operation
G. Changing Adjustable Parameters (continued)
Central Heat
Setpoint
Heating Element Type
Central Heat
Setpoint
Heating Element Type
180°F to 190°F
(82.2°C to 87.8°C)
Fan Coil
100°F to 140°F
(37.8°C to 60°C)
In Slab Radiant High
Mass Radiant
160°F to 190°F
(71.1°C to 87.8°C)
Convection
Baseboard
Fin Tube
Convective
130°F to 160°F
(54.4°C to 71.1°C)
Staple-up Radiant
Low Mass Radiant
130°F to 160°F
(54.4°C to 71.1°C)
Radiant
Baseboard
140°F to 160°F
(60°C to 71.1°C)
Radiators
Figure 40: Outdoor Reset Curve
Outdoor Air Temperature
-20
10
5
-15 -10 -5
0
110
45
40
20 25 30 35
55 60 65
70
15
50
145
115
150
120
140
135
130
125
155
190
160
195
165
185
180
175
170
200
Boost Maximum Off Point
=
Central Heat Setpoint
minus Diff Above
Low Boiler Water Temp
Default
=
110 F
High Outside Air Temp
Default
=
70 F
10 F
H
ot
W
at
er
S
et
po
in
t
Minimum Water Temperature
Default
=
130 F
TOD Setback Setpoint
Default
=
170 F
Central Heat Setpoint
Low Outside Air Temp
=
180 F & 0 F
Default Outdoor Air Reset Setpoint
(Shown Bold)
Default Boost Outdoor Air Reset Setpoint
(
Shown with thin lines
, typical)
(
Reset setpoint increased by
10 F every
20
minutes that demand is not satisfied
.
Boost Time is field selectable
between
0 to 30 minutes)
75
Summary of Contents for APEX
Page 57: ...57 VIII Electrical continued Figure 26 Ladder Diagram ...
Page 58: ...58 VIII Electrical continued ...
Page 59: ...59 Figure 27 Wiring Connections Diagram VIII Electrical continued ...
Page 105: ...105 ...
Page 109: ...109 XIII Repair Parts continued APX625 APX725 and APX825 APX825 shown ...
Page 112: ...112 XIII Repair Parts continued APX425 and APX525 ...
Page 114: ...114 XIII Repair Parts continued APX625 APX725 and APX825 ...
Page 122: ...122 ...
Page 123: ...123 ...