10
I. Product Description, Specifications and Dimensional Data
(continued)
Table 2: Ratings
Apex Series Gas-Fired Boilers
Model
Number
Input (MBH)
Gross Output
(MBH)
Net Ratings Water
1
(MBH)
Thermal
Efficiency (%)
Combustion
Efficiency (%)
Min.
Max.
APX425
80
399
375
326
94.1
94.5
APX525
100
500
475
413
95.0
95.0
APX625
125
625
594
516
95.0
96.0
APX725
145
725
689
599
95.0
95.0
APX825
160
800
760
661
95.0
93.0
Ratings shown are for installations at sea level and elevations up to 2000 ft. For elevations above 2000 ft., the boiler will naturally
derate by 2.5% for each 1000 ft. above sea level.
1
Net AHRI Water Ratings based on allowance of 1.15. Consult manufacturer before selecting boiler for installations having
unusual piping and pickup requirements, such as intermittent system operation, extensive piping systems, etc.
II. Unpacking Boiler
NOTICE
Do not drop boiler.
A. Move boiler
to approximate installed position.
B. Remove all
crate fasteners.
C. Lift and remove
outside container.
D. Remove boiler
from cardboard positioning sleeve
on shipping skid.
E. Move boiler
to its permanent location.
Summary of Contents for APEX
Page 57: ...57 VIII Electrical continued Figure 26 Ladder Diagram ...
Page 58: ...58 VIII Electrical continued ...
Page 59: ...59 Figure 27 Wiring Connections Diagram VIII Electrical continued ...
Page 105: ...105 ...
Page 109: ...109 XIII Repair Parts continued APX625 APX725 and APX825 APX825 shown ...
Page 112: ...112 XIII Repair Parts continued APX425 and APX525 ...
Page 114: ...114 XIII Repair Parts continued APX625 APX725 and APX825 ...
Page 122: ...122 ...
Page 123: ...123 ...