30
IV. Venting
D. Stainless Steel Venting (continued)
Vent System
Component
Part
Numbers
Equivalent
Length of Pipe
APX425 and
APX525
4 In. Vent
SS Vent Kit
102501-02
N/A
Horizontal Vent Terminal
(Included in Kit)
8116313
PVC to SS Vent Adapter
(Included In Kit)
102220-01
Vertical Vent Terminal
102680-02
Pipe
x
1 ft. (0.3 m)
100176-01 1 ft. (0.3 m)
Pipe
x
3 ft. (0.9 m)
100177-01 3 ft. (0.9 m)
Pipe
x
5 ft. (1.5 m)
100178-01 5 ft. (1.5 m)
Pipe x Adjustable
100179-01
Equal to
Installed Length
1.06 to 1.64 ft.
(0.3 m to 0.5 m)
90° Elbow
100180-01
8 ft. (2.4 m)
45° Elbow
100181-01
4.5 ft. (1.4 m)
Horizontal Drain Tee
100182-01
2 ft. (0.6 m)
Vertical Drain Tee
100183-01
7.5 ft. (2.3 m)
Single Wall Thimble
100184-01
N/A
Table 11A: Thermal Solutions Vent System
Components (Stainless Steel, 4 in. only)
Manufacturer
Vent
System
Nominal Dia.
PVC to SS
Adapter
Wall Thimbles
Horizontal
Termination
Vertical
Termination
M&G/DuraVent
FasNseal
4 in.
(100 mm)
810005231
FSWT4
Tee: FSTT4
FSBS4
6 in.
(150 mm)
810005545
FSWT6
Tee: FSTT6
FSBS6
Z-Flex
SVE Series III
(“Z-Vent III”)
4 in.
(100 mm)
2SVSTTA04.5
2SVSWTF04
Tee: 2SVSTTX04
2SVSTPX04
6 in.
(150 mm)
2SVSTTA06.5
2SVSWTF06
Tee: 2SVSTTX06
2SVSTPX06
NOTE: See vent system manufacturer’s literature for other part numbers that are required such as straight pipe, elbows, firestops
and vent supports.
Table 11B: Alternate Vent Systems and Vent Components (Stainless Steel)
Figure 16: Field Installation of Two-Pipe Vent
System Adapter for Stainless Steel
c. Where the use of “silicone” is called for in the
following instructions, use GE RTV 106 or
equivalent for the vent collar. Seal galvanized
combustion air piping sections with any general-
purpose silicone sealant such as GE RTV102.
Seal PVC combustion air piping sections with
PVC cement.
d. Do not drill holes in vent pipe.
2. Field Installation of CPVC/PVC Two-Pipe
Vent System Connector and PVC to Stainless
Steel Adapter
a. Install CPVC/PVC two-pipe vent system
connector. Follow instructions in “2. Field
Installation of CPVC/PVC Two-Pipe Vent
System Connector” under “B. CPVC/PVC
Venting.” See also Figures 9 and 16.
b.
Models APX425 and APX525 only:
Apply
provided dielectric grease (grease pouch taped to
the vent system connector) all around to the vent
or air connection inner red silicon gasket.
c.
Models APX625, APX725 and APX825
only:
Apply a coating of supplied red RTV
silicone sealant, at least 1 in. (25 mm) wide,
around circumference of PVC to stainless steel
adapter male end.
d. Push and twist PVC to stainless steel adapter
into two-pipe vent system connector vent or
combustion air supply port until bottomed out.
See Figure 16.
e. Tighten the worm band clamp screw to secure
PVC to stainless steel adapter.
f. Do not install PVC to stainless steel adapter
at the lower combustion air supply port of the
two-pipe vent system connector when using PVC
pipe for combustion air supply to boiler.
Summary of Contents for APEX
Page 57: ...57 VIII Electrical continued Figure 26 Ladder Diagram ...
Page 58: ...58 VIII Electrical continued ...
Page 59: ...59 Figure 27 Wiring Connections Diagram VIII Electrical continued ...
Page 105: ...105 ...
Page 109: ...109 XIII Repair Parts continued APX625 APX725 and APX825 APX825 shown ...
Page 112: ...112 XIII Repair Parts continued APX425 and APX525 ...
Page 114: ...114 XIII Repair Parts continued APX625 APX725 and APX825 ...
Page 122: ...122 ...
Page 123: ...123 ...