52
Table 16B: Maximum Capacity of Schedule 40 Black Pipe in CFH* (LP Gas) For Gas Pressures
of 1/2 psi (3.4 kPa) or Less
Inlet Pressure 11.0 in wc (2.7 kPa); 0.3 in wc (0.07 kPa) Pressure Drop
Nominal Pipe
Size, In.
Inside
Diameter, In.
Length of Pipe, Ft.
10
20
30
40
50
60
70
80
90
100
½
0.622
88
60
48
41
37
33
31
29
27
25
¾
0.824
184
126
101
87
77
70
64
60
56
53
1
1.049
346
238
191
163
145
131
121
112
105
100
1¼
1.380
710
488
392
336
297
269
248
231
216
204
1½
1.610
1064
732
588
503
446
404
371
346
324
306
2
2.067
2050
1409
1131
968
858
778
715
666
624
590
2½
2.469
3267
2246
1803
1543
1368
1239
1140
1061
995
940
3
3.068
5776
3970
3188
2729
2418
2191
2016
1875
1760
1662
Inlet Pressure 11.0 in wc (2.7 kPa); 0.5 in wc (0.12 kPa) Pressure Drop
Nominal Pipe
Size, In.
Inside
Diameter, In.
Length of Pipe, Ft.
10
20
30
40
50
60
70
80
90
100
½
0.622
116
80
64
55
48
44
40
38
35
33
¾
0.824
242
166
134
114
101
92
85
79
74
70
1
1.049
456
314
252
215
191
173
159
148
139
131
1¼
1.380
937
644
517
442
392
355
327
304
285
269
1½
1.610
1403
964
775
663
588
532
490
456
427
404
2
2.067
2703
1858
1492
1277
1131
1025
943
877
823
778
2½
2.469
4308
2961
2377
2035
1803
1634
1503
1399
1312
1239
3
3.068
7615
5234
4203
3597
3188
2889
2658
2472
2320
2191
* 1 CFH of LP Gas is approximately equal to 2.5 MBH; contact your gas supplier for the actual heating value of your gas.
Table 17: Equivalent Lengths of Standard Pipe Fittings & Valves (ft)
Nominal
Pipe Size,
Inc.
Inside
Diameter,
In.
Valves (Screwed) - Fully Open
Screwed Fittings
Gate
Globe
Angle
Swing
Check
45°
Elbow
90°
Elbow
180 Close
Return Bend
90 Tee Flow
Through
Run
90 Tee, Flow
Through
Branch
½
0.622
0.4
17.3
8.7
4.3
0.7
1.6
3.5
1.6
3.1
¾
0.824
0.5
22.9
11.4
5.7
1.0
2.1
4.6
2.1
4.1
1
1.049
0.6
29.1
14.6
7.3
1.2
2.6
5.8
2.6
5.2
1¼
1.38
0.8
38.3
19.1
9.6
1.6
3.5
7.7
3.5
6.9
1½
1.61
0.9
44.7
22.4
11.2
1.9
4.0
9.0
4.0
8.0
2
2.067
1.2
57.4
28.7
14.4
2.4
5.2
11.5
5.2
10.3
2½
2.469
1.4
68.5
34.3
17.1
2.9
6.2
13.7
6.2
12.3
3
3.068
1.8
85.2
42.6
21.3
3.6
7.7
17.1
7.7
15.3
For materials or conditions other than those listed
above, refer to
National Fuel Gas Code
, ANSI Z223.1/
NFPA 54 or
Natural Gas and Propane Installation
Code
, CAN/CSA B149.1, or size system using standard
engineering methods acceptable to authority having
jurisdiction.
B. Connect boiler gas valve to gas supply
system.
VII. Gas Piping
(continued)
Summary of Contents for APEX
Page 57: ...57 VIII Electrical continued Figure 26 Ladder Diagram ...
Page 58: ...58 VIII Electrical continued ...
Page 59: ...59 Figure 27 Wiring Connections Diagram VIII Electrical continued ...
Page 105: ...105 ...
Page 109: ...109 XIII Repair Parts continued APX625 APX725 and APX825 APX825 shown ...
Page 112: ...112 XIII Repair Parts continued APX425 and APX525 ...
Page 114: ...114 XIII Repair Parts continued APX625 APX725 and APX825 ...
Page 122: ...122 ...
Page 123: ...123 ...