USER MANUAL - 230 VAC MULTIFUNCTION CONTROL UNIT - 051D 

GENERAL FUNCTIONS

L4

RESTORING MANOEUVRE

WITH DEAD MAN FUNCTION

MINIMUM: 

n

MAXIMUM: 

y

This function, if enabled, 

L4

 = 

Y

 allows the gate to be opened or closed if one of the safety devices (photocells or stop) breaks down, 

allowing passage until the fault is repaired. This mode requires the installation of a START device (normally open contact) on terminal block 
9 or terminal block 10 and the setting of its management parameter (

e1

 or 

e2

) to one of the following functions: 

go

 start, 

op

 open or 

cL

 close. If the conditions described above are met and a safety device (stop, external or internal photocell) has been active for more than 

5 seconds, then it is possible to operate the gate in opening/closing mode using this procedure:
1. Activate the START device
2. Deactivate the START device
The flashing lights turn on (only if configured on terminals 20 + e 21 - (

L0

) via function

L0

 = 

02

 or 

L0

 = 

03

).

3. Activate the START device within 2.5 seconds of the flashing light coming on. The control unit shows the countdown from 2.5 to 0 sec-
onds on the display.
4. The gate will perform the required operation (opening/closing) as long as the START device is kept active. When the START device is 
deactivated, the control unit blocks the movement of the gate.

L5

WORKING CYCLES LIMIT - MAINTENANCE 

REQUEST

MINIMUM: 

n

MAXIMUM: 

5.9

Parameter 

L5

 allows the number of working cycles before maintenance to be set. When the gate has performed 

L5

 operation, the time 

for flashing will be set to 5 seconds. This function can be useful for alerting the end user to the need for system maintenance. The parameter 

L5

 can be set in these ranges:

n

 = disabled

- from 

0.1

 to 

0.9

 from 1 to 9 working cycles

- from 

1.1

 to 

1.9

 from 10 to 90 working cycles

- from 

2.1

 to 

2.9

 from 100 to 900 working cycles

- from 

3.1

 to 

3.9

 from 1000 to 9000 working cycles

- from 

4.1

 to 

4.9

 from 10000 to 90000 working cycles

- from 

5.1

 to 

5.9

 from 100 000 to 900 000 working cycles

Pressing any key on the control unit sets the counter to 0 and this function will only be activated again after 

L5

 cycles.

L6

WORKING CYCLES COUNTER

MINIMUM: 

0.1

MAXIMUM: 

6.9

Parameter 

L6

 cannot be changed or deleted and represents the number of working cycles of the automatic gate. Once the parameter 

L6

 has been selected (see the MENU NAVIGATION page) the most significant decimal number of the counter is shown in the format 

POSITION, VALUE. By pressing the (

-

) KEY the display switches off.

Once the (

-

) KEY is released the scanning of the counter begins displaying its

decimal position (value to the left of the dot) and its value (to the right of the dot).

EXAMPLE:

if a gate has performed 6258 operations, once 

L6

 has been selected the display shows: 

3.6

 by pressing the (

-

) KEY the display switches 

off. By releasing the (

-

) KEY the display will show in sequence:

multiplier:

*1000

*100

*10

*1

position:

3

2

1

0

3.6

2.2

1.5

0.8

value:

6

2

5

8

= 1000*6 + 100*2 + 10*5 + 1*8

The display changes screen to the next position approximately every 3 seconds, switching off briefly before showing the new number. 

How to read the display:

the first digit indicates the exponent of the 
power of 10, the second its multiplier.

For example:

3.3 indicates 103 x 3 = 3,000
2.9 indicates 103 x 9 = 900
5.1 indicates 105 x 1 = 100,000

Summary of Contents for 051D

Page 1: ...n inputs Positive or negative inputs Dead man s function Soft start Technical data Motors 600W each motors Flashing lamp max 60W 230 VAC Power supply 24 VDC max 250mA AB2101 VERSION APE 570 0510 with radio module APE 570 0511 without radio module USER MANUAL AB00093 rev 02 del 01 2022 1 motor mode Flashing light 230 vac vdc Photocells test Motors test Compatible with plug in Faac radio receiver Te...

Page 2: ...QUE ADJUSTMENT STANDARD FORCE 17 TORQUE ADJUSTMENT SLOWDOWN FORCE 17 STANDARD OBSTACLE TRESHOLD 17 SLOWDOWN OBSTACLE TRESHOLD 17 OBSTABLE SENSOR PROGRAMMING 18 AUTOMATIC OBSTACLE SENSOR PROGRAMMING 18 FUNCTION OVERVIEW 19 AUTO CLOSE TIME 19 PEDESTRIAN TIME 19 KICK BACK FUNCTION AT CLOSING 19 PRE BLINKING TIME 19 KICK BACK FUNCTION AT OPENING 19 STEP BY STEP MODE 19 COMMUNITY MODE 19 STANDARD MODE ...

Page 3: ...polar switch with contact opening distance equal to or greater than 3 mm should be installed on the power supply of the automatic gate The use of a 6A thermomagnetic circuit breaker with omnipolar switch is recommended 12 Check that there is a differential switch with a 0 03A threshold upstream of the system 13 Check that the earthing system is properly installed and connected to the metal parts o...

Page 4: ...PS MOTOR B MOTOR A THE LIGHT IS OPEN WHEN ONE OF THE TWO MOTORS IS MOVING GENERAL PE N L GROUND NEUTRAL PHASE MOTOR A 600 W 230 VAC 1 2 3 COMMON OPEN CLOSE MOTOR B 600 W 230 VAC 4 5 6 COMMON OPEN CLOSE LIGHT 60 W 230 VAC 7 8 COMMON OPEN PLUG IN FOR RECEIVER FUSE 5A 230 VAC PLUG IN FOR RECEIVER 2 ...

Page 5: ...YOUT TYPICAL SWING GATE INSTALLATION The system must have a physical limit in the opening and closing movement Antenna Flashing lamp Motor B Closing photocells Pedestrian access INTERNAL AREA OF THE GATE opening photocells Motor A opens first Motor A opens first 051D MDR ...

Page 6: ...13 14 15 16 17 18 19 20 21 TRANSMITTER GATE ELECTRIC LOCK FLASHING LAMP STEADY LIGHT FLASHING LIGHT PHOTOCELL OPENING PHOTOCELL CLOSING STOP START PEDESTRIAN LIMIT SWITCH OPENING LIMIT SWITCH CLOSING LIMIT SWITCH OPENING LIMIT SWITCH CLOSING To use the PHOTOCELL TEST FUNCTION connect the negative pole of the transmitters to the t1 terminal block and activate this function with t1 Y ...

Page 7: ...13 14 15 16 17 18 19 20 21 TRANSMITTER GATE ELECTRIC LOCK FLASHING LAMP STEADY LIGHT FLASHING LIGHT PHOTOCELL OPENING PHOTOCELL CLOSING STOP START PEDESTRIAN LIMIT SWITCH OPENING LIMIT SWITCH CLOSING LIMIT SWITCH OPENING LIMIT SWITCH CLOSING To use the PHOTOCELL TEST FUNCTION connect the negative pole of the transmitters to the t1 terminal block and activate this function with t1 Y ...

Page 8: ...etected by the control unit that sets the parameter of the terminal block to the correct safety fuction in this case E3 St STOP This feature is called AUTO ENABLE E4 TERMINAL BLOCK 12 E4 NORMALLY CLOSED Terminal block 12 is associated with a normally closed N C contact The parameters that can be set are N DISABLED tc CLOSING PHOTOCELL MODE 1 and td CLOSING PHOTOCELL MODE 2 This control unit is sup...

Page 9: ...ith a normally closed N C contact The parameters that can be set are n DISABLED ob LIMIT SWITCH OPENING MOTOR B This control unit is supplied with the standard setting where terminal block 24 is disabled E9 n When a NORMALLY CLOSED contact is connected to terminal block 24 it is automatically detected by the control unit that sets the parameter of the terminal block to the correct safety fuction i...

Page 10: ...i scorre la lista dei parametri velocemente 2 Dopo circa 2 secondi il display mostrerà il valore di F0ad esempio10 secondi 3 Mantenere premuto il TASTO La centrale incrementerà velocemente il valore fino a che non mostrerà 5t Quando il display mostrerà 5t la CHIUSURA AUTOMATICA sarà disabilitata e il cancello rimarrà aperto al termine della fase di apertura 5 5t t indica STOP al termine dell apert...

Page 11: ...r B standard time A1 b1 slowdown time A2 b2 and auto close time F0 configuration If you disabled the slowdown time of one of the motors or both ignore A1 and or b1 _ _ After 2 seconds two dashes will appear on the display Perform a START command to start A1 configuration A1 You are working on motor A STANDARD TIME Motor A starts the opening movement When the leaf controlled by motor A has complete...

Page 12: ... TESTS t1 PHOTOCELLS TEST t2 MOTORS TEST d FACTORY SETTINGS d0 RESTORING INITIAL VALUES p GUIDED PROGRAMMING p1 GUIDED PROGRAMMING 1 MOTOR p2 GUIDED PROGRAMMING 2 MOTORS p6 OBSTACLE SENSOR PROGRAMMING KEYS RUN FROM p6 TO a1 RUN FROM a1 TO p6 INCREASE ENABLE INCREASE ENABLE o PROGRAMMABLE OUTPUTS o1 RELAY MODULE FUNCTION PLUG IN 1 o2 RELAY MODULE FUNCTION PLUG IN 2 r RADIO r0 GATE CODE r1 START r2 ...

Page 13: ...ERMINAL 11 DISABLED E4 n TERMINAL 12 DISABLED E5 n TERMINAL 13 DISABLED E6 n TERMINAL 22 DISABLED E7 n TERMINAL 23 DISABLED E8 n TERMINAL 24 DISABLED E9 n TERMINAL 25 DISABLED The procedures that restore the factory settings can be identified on the menu by the letter d d0 RESTORATION OF INITIAL PARAMETER SETTINGS This procedure DOES NOT DELETE previously saved remote controls from the memory To r...

Page 14: ... OPENING PHOTOCELL CLOSING PHOTOCELL The OPENING PHOTOCELL and CLOSING PHOTOCELL MODE 1 functions are active at the same time e4 12 e5 13 tc CLOSING PHOTOCELL MODE 1 The CLOSING PHOTOCELL MODE 1 function reverses the move ment during the closing phase and it has no effect during the opening phase If the CLOSING PHOTOCELL MODE 1 function is active and the gate is stopped it will NOT be started in O...

Page 15: ... is reported after automatic programming of SENSOR p6 Error 9P indicates that one or more parameters related to the obstacle sensor have not been calibrated To check which parameters are not programmed check the value of the following parameters p6 p7 b7 and b8 see CONFIG URATION MOTOR A B The parameters set to n have not been programmed ab LIMIT SWITCH MOTOR A LIMIT SWITCH MOTOR B The function LI...

Page 16: ... STANDARD FORCE MINIMUM 01 10 MAXIMUM 10 100 During STANDARD TIME A1 the force of motor A is A5 of the total The force of motor A can be set from 10 to 100 in steps of 10 The force of the motor increases or decreases the sensitivity of the obstacle sensor the greater the force set the lower the sensitivity the lower the force set the higher the sensitivity A6 TORQUE ADJUSTMENT STANDARD FORCE MINIM...

Page 17: ...om 10 to 100 in steps of 10 The force of the motor increases or decreases the sensitivity of the obstacle sensor The greater the force set the lower the sensitivity The lower the force the greater the sensitivity b6 TORQUE ADJUSTMENT STANDARD FORCE MINIMUM 01 10 MAXIMUM 10 100 During SLOWDOWN TIME b2 the force of the motor is b6 of the total The SLOWDOWN FORCE can be set from 10 to 100 in steps of...

Page 18: ...ue If they are set to n that parameter has not been programmed Changing the force of the motor may change the programming result Example When programming is complete the display shows9p Suppose that the normal force of motor B has not been programmed The numbers given in the example are for illustration purposes only and may vary from installation to installation At the end of procedure p6 the con...

Page 19: ...RIAN order behaves exactly like a START order f2 KICK BACK MINIMUM 0 0sec MAXIMUM 2 5 sec At the end of the closing process after having performed any slowing down phase motor A pushes on the stop at maximum force for F2 se conds This function can be useful when using the electric lock when closing is difficult During this operation the obstacle sensor is disabled f3 PRE BLINKING TIME MINIMUM 0 0 ...

Page 20: ...ic lock can also be controlled by remote control L0 00 The output is disabled Only remote controls associated with the function EL activate the electric lock for 3 seconds can activate the control unit s output 20 e 21 L0 The activation of the electric lock by remote control can be useful to manage a pedestri an gate adjacent to the automatic gate L0 01 The output is enabled to manage an electric ...

Page 21: ...ds This function can be useful for alerting the end user to the need for system maintenance The parameter L5 can be set in these ranges n disabled from 0 1 to 0 9 from 1 to 9 working cycles from 1 1 to 1 9 from 10 to 90 working cycles from 2 1 to 2 9 from 100 to 900 working cycles from 3 1 to 3 9 from 1000 to 9000 working cycles from 4 1 to 4 9 from 10000 to 90000 working cycles from 5 1 to 5 9 fr...

Page 22: ...uccessful the required operation is started If the check fails the control unit display will indicate 1t and the gate will not be started The photocell test will only be carried out on installed photocells For example if the system only uses the photocell when closing ensure that parameter e4 is set to tC or td functions relating to the photocell and that the parameter e5 is disabled e5 n see GENE...

Page 23: ...ciated is displayed SAVING A REMOTE CONTROL AS START 1 Select the parameter r1 using the scroll keys or 2 After a few seconds the display shows _ 3 Hold down the button on the remote control to be stored The display shows _ 4 Press the KEY on the control unit The display shows 1 The remote control has been successfully stored in position 1 of the con trol unit memory display 2 memory position 2 di...

Page 24: ...d as described in the STORE A REMOTE CONTROL paragraph To ASSOCIATE A NEW FUNCTION select parameter r6 or r7 Hold down the KEY The display starts flashing showing r6 or r7 When it stops flashing release the KEY Change the function using the KEY The function initially associated with r6 is po DEAD MAN OPENING The function initially associated with r7 is pC DEAD MAN CLOSING r9 PLUG IN RADIO The PLUG...

Page 25: ...trolling an electric lock through a radio device or for signalling a dead man opening closing movement USCITE PROGRAMMABILI I parametri di gestione delle uscite programmabili sono identificabili sul menù dalla lettera O Per poter usare queste funzioni sono necessari dei moduli di espansione RELAY APE 570 0022 da collegare ai di connessione presenti sulla centrale o1 o2 USCITE PROGRAMMABILI 1 e 2 L...

Page 26: ...Using the KEYS select the Po function 6 Using KEYS select the parameter o1 o2 7 Using the KEYS select the 06 function 8 Exit the menu using the KEYS When the remote control button stored following the above procedure is transmitting the gate will move in the OPEN direction and simultaneously the output will be activated EXAMPLE configure a remote control to signal a dead man closing movement 1 Sto...

Page 27: ...mbiente e sulla salute e favorisce il reimpiego e o riciclo dei materiali di cui è composta l apparecchiatura Lo smaltimento abusivo del prodotto da parte dell utente comporta l applicazione delle sanzioni di cui alla corrente normativa di legge www abtecno com 27 27 PRODUCT DISPOSAL A Declaration for household EEE without batteries or portable accumulators INFORMATION FOR USERS OF DOMESTIC OR PRO...

Page 28: ...AUTOMATION ACCESSORIES ABEXO is a registered trademark property of AB TECNO srl Via Cicogna 95 40068 San Lazzaro di Savena BO info abtecno com www abexo tech ...

Reviews: