USER MANUAL - 230 VAC MULTIFUNCTION CONTROL UNIT - 051D
TERMINAL BLOCK SETTINGS
E7
TERMINAL BLOCK 22 - E7 - NORMALLY CLOSED
Terminal block 22 is associated with a normally closed (N.C.) contact. The parameters that can be set are:
n
DISABLED,
Ac
LIMIT SWITCH CLOSING MOTOR A. This control unit is supplied with the standard setting where terminal block
22 is disabled (
E7
=
n
). When a NORMALLY CLOSED contact is connected to terminal block 22, it is automatically detected by
the control unit that sets the parameter of the terminal block to the correct safety fuction, in this case
E7
=
Ac
LIMIT SWITCH
CLOSING MOTOR A. This feature is called AUTO-ENABLE.
E8
TERMINAL BLOCK 23 - E8 - NORMALLY CLOSED
Terminal block 23 is associated with a normally closed (N.C.) contact. The parameters that can be set are:
n
DISABLED,
ob
LIMIT SWITCH OPENING MOTOR B. This control unit is supplied with the standard setting where terminal block
23 is disabled (
E8
=
n
). When a NORMALLY CLOSED contact is connected to terminal block 23, it is automatically detected by
the control unit that sets the parameter of the terminal block to the correct safety fuction, in this case
E8
=
ob
LIMIT SWITCH
OPENING MOTOR B. This feature is called AUTO-ENABLE.
E9
TERMINAL BLOCK 24 - E9 - NORMALLY CLOSED
Terminal block 24 is associated with a normally closed (N.C.) contact. The parameters that can be set are:
n
DISABLED,
ob
LIMIT SWITCH OPENING MOTOR B. This control unit is supplied with the standard setting where terminal block
24 is disabled (
E9
=
n
). When a NORMALLY CLOSED contact is connected to terminal block 24, it is automatically detected by
the control unit that sets the parameter of the terminal block to the correct safety fuction, in this case
E9
=
ob
LIMIT SWITCH
OPENING MOTOR B. This feature is called AUTO-ENABLE.
The standard setting of inputs is negative common
E0
=
02
. To set the inputs with positive common, change to
E0
=
01
.
E1
N.O.
E2
N.O.
E3
N.C.
E4
N.C.
E5
N.C.
n
DISABLED
Go
START
PE
PEDESTRIAN
oP
OPEN
cL
CLOSE
Po
OPEN DEAD MAN
Pc
CLOSE DEAD MAN
EL
ELECTRIC LOCK
n
DISABLED
Go
START
PE
PEDESTRIAN
oP
OPEN
cL
CLOSE
Po
OPEN DEAD MAN
Pc
CLOSE DEAD MAN
EL
ELECTRIC LOCK
n
DISABLED
ST
(*) STOP
n
DISABLED
tc
(*) CLOSING
PHOTOCELL
MODE 1
td
CLOSING
PHOTOCELL
MODE 2
n
DISABLED
ta
(*) OPENING
PHOTOCELL
tc
CLOSING
PHOTOCELL
MODE 1
E6
N.C.
E7
N.C.
E8
N.C.
E9
N.C.
n
DISABLED
Ao
(*) LIMIT SWITCH
OPENING
MOTOR A
n
DISABLED
AC
(*) LIMIT SWITCH
CLOSING
MOTOR A
n
DISABLED
ob
(*) LIMIT SWITCH
OPENING
MOTOR B
n
DISABLED
ob
(*) LIMIT SWITCH
OPENING
MOTOR B
STANDARD TERMINAL BLOCKS CONFIGURATION OR WHEN RESTORED TO FACTORY SETTINGS
* N.C. inputs are disabled, as standard configuration:
E3
=
E4
=
E5
=
E6
=
E7
=
n
.
When the inputs are connected, the control unit automatically sets them to the correct safety function.
N.O. = NORMALLY OPEN
N.C. = NORMALLY CLOSED