USER MANUAL - 230 VAC MULTIFUNCTION CONTROL UNIT - 051D
GENERAL FUNCTIONS
There are many functions that allow the operation of the gate to be customised. These are identified within the menu by the letters
F
and
L
.
sec = seconds % = percentage parameter n = disabled xxx = see full description
Times are expressed in seconds
Forces and thresholds are expressed in decimals and correspond to %. Ex:
01
= 10%
f0
AUTO-CLOSE TIME
10 sec
f8
PHOTOCELLS LOGIC: SLIDING
n (y/n)
f1
PEDESTRIAN TIME
7 sec
f2
KICK BACK FUNCTION AT CLOSING
0,0 sec
l0
ELECTRIC LOCK - FLASHING LIGHT 12VDC
0
f3
PRE-BLINKING TIME
1,0 sec
l1
MOTOR HEATING/OIL RECYCLING
0 min
f4
KICK BACK FUNCTION AT OPENING
n (y/n)
l3
ONLY MOTOR A MODE
n (y/n)
f5
STEP-BY-STEP MODE
n (y/n)
l4
RESTORING MANOEUVRE WITH DEAD MAN FUNCTION
n (y/n)
f6
MULTIPLE RESIDENTS MODE
n (y/n)
l5
WORKING CYCLES LIMIT - MAINTENANCE REQUEST
n
f7
FAST CLOSURE
n (y/n)
l6
TOTAL WORKING CYCLES COUNTER
xx
f0
AUTO-CLOSE TIME
MINIMUM:
0.0
sec
MAXIMUM:
99
sec
After opening, the gate remains fully open for
F0
seconds. At the end of this time, the gate begins to close. To disable the AUTOMATIC
CLOSE TIME keep the (+) KEY pressed down for a long time, until the display shows
st
. If automatic closing is disabled, the gate remains
open after opening has finished.
f1
PEDESTRIAN TIME
MINIMUM:
0.0
sec
MAXIMUM:
a1
sec
In the event that the gate is started by a PEDESTRIAN order,
F1
represents the working time of motor A. The slowdown will not be perfor-
med during the opening phase, but will be performed during the closing phase. During a PEDESTRIAN operation, motor B is not activated.
A START order interrupts the PEDESTRIAN operation and also starts motor B. During a standard working cycle, the PEDESTRIAN order
behaves exactly like a START order.
f2
KICK BACK
MINIMUM:
0.0
sec
MAXIMUM:
2.5
sec
At the end of the closing process, after having performed any slowing down phase, motor A pushes on the stop at maximum force for
F2
se-
conds. This function can be useful when using the electric lock, when closing is difficult. During this operation, the obstacle sensor is disabled
f3
PRE-BLINKING TIME
MINIMUM:
0.0
sec
MAXIMUM:
5.0
sec
Before starting an opening or closing operation, the gate waits for
F3
seconds.
f4
KICK BACK
MINIMUM:
n
MAXIMUM:
y
By enabling parameter
F5
=
y
before opening, motor A closes for 0.5 seconds. During this time the force of the motor is at its maximum
and the obstacle sensor is disabled. This function can be useful to help release the electric lock.
f5
STEP-BY-STEP MODE
MINIMUM:
n
MAXIMUM:
y
Enabling parameter
F5
=
y
activates the STEP-BY-STEP mode: during the opening and closing phase, the START orders stop the move-
ment. A subsequent START order will start the movement in the opposite direction to the one that was interrupted.
For example: if the gate is opening, a START order stops the opening. The subsequent START order starts the closing phase of the gate.
f6
MULTIPLE RESIDENTS MODE
F5
=
n
F6
=
n
Enabling parameter
F6
=
Y
activates the MULTIPLE RESIDENTS mode: during the OPENING phase, the START orders do not block the
operation. During the closing phase, the START orders reverse the movement (from CLOSING
(
→
)
OPENING). Multiple residents mode
has higher priority than STEP-BY-STEP mode. By setting
F6
=
y
it will no longer be possible to change the value of
F5
which will be
automatically disabled (
n
).
STANDARD MODE
MINIMUM:
00
= 0%
MAXIMUM:
n
= disabled
If both STEP-BY-STEP and COMMUNITY modes are disabled (
F5
=
n
,
F6
=
n
) the operating logic of the control unit is STANDARD: du-
ring opening, the START orders stop the movement of the gate. During closing, the START orders reverse the movement.