14
USER MANUAL - 230 VAC MULTIFUNCTION CONTROL UNIT - 051D
OPERATIONAL REPORTS AND PRIORITIES
When you are not navigating through the menu, the display shows the operating function. If multiple functions are active, the
one with the higher priority is shown. For example, input 9 on the terminal block is associated with the function programmed on
parameter
e1
. The value
e1
in the initial configuration is
e1
=
go
START. The START function is associated with a normally
open contact; when the contact is closed, the control unit display shows
go
, i.e. it indicates that an event has been generated that
activates the START function. If shortly afterwards, a remote control button is pressed which has been stored with the function
r2
STOP. The control unit display shows
st
STOP, because the STOP function has a higher priority than the STOP function.
The following table lists all the operational functions that the control unit is able to manage, starting with the highest priority
and ending with the lowest.
DISPLAY
NAME
DESCRIPTION
CONTROL SOURCE
TERMINAL BLOCK
REMOTE CONTROL
po
DEAD MAN OPENING
When the DEAD MAN OPENING function is active, the gate is open
even if the STOP and PHOTOCELLS functions are active. When the
DEAD MAN OPENING function is no longer engaged, the gate
stops.
e1
9
e2
10
r6
r7
pc
DEAD MAN CLOSING
When the DEAD MAN CLOSING function is active, the gate is
closed even if the STOP and PHOTOCELLS functions are active.
When the DEAD MAN CLOSING function is no longer engaged,
the gate stops.
e1
9
e2
10
r6
r7
ST
STOP
The STOP function is active. If the gate is moving, it will come to a
stop.
e3
11
r2
f5
OPENING
PH
CLOSING PHOTOCELL
The OPENING PHOTOCELL and CLOSING PHOTOCELL MODE 1
functions are active at the same time.
e4
12
e5
13
tc
CLOSING PHOTOCELL
MODE 1
The CLOSING PHOTOCELL MODE 1 function reverses the move-
ment during the closing phase and it has no effect during the
opening phase. If the CLOSING PHOTOCELL MODE 1 function is
active and the gate is stopped, it will NOT be started in OPEN when
a START order is received.
e4
12
e5
13
td
CLOSING PHOTOCELL
MODE 2
The CLOSING PHOTOCELL MODE 2 function reverses the move-
ment during the closing phase and it has no effect during the
opening phase. If the CLOSING PHOTOCELL MODE 2 function is
active and the gate is stopped, it will be started in OPEN when a
START order is received.
e4
12
ta
OPENING PHOTOCELL The OPENING PHOTOCELL function reverses the movement dur-
ing the closing phase suspends opening during the opening phase.
e5
13
1H
LIMIT SWITCH ERROR
MOTOR A and MOTOR
B
The OPENING LIMIT SWITCH and CLOSING LIMIT SWITCH func-
tions of motor A and motor B are active simultaneously. Motor
A and motor B will not be able to move when both opening or
closing.
e6
22
e8
24
e7
23
e9
25
ea
LIMIT SWITCH ERROR
MOTOR A
The OPENING LIMIT SWITCH and CLOSING LIMIT SWITCH func-
tions of motor A are active simultaneously. Motor A will not be
able to move when both opening or closing.
e6
22
e7
23
eb
LIMIT SWITCH ERROR
MOTOR A B
The OPENING LIMIT SWITCH and CLOSING LIMIT SWITCH func-
tions of motor B are active simultaneously. Motor B will not be
able to move when both opening or closing.
e8
24
e9
25
go
START
The START function can open and close the gate. Its operation
also depends on the programming of the parameters made (
F5
=
step-by-step mode /
F6
=multiple residents mode - see “GENER-
AL FUNCTIONS”) and on the status of the other inputs.
e1
9
e2
10
r1
r4