TBN580 TRANSMITTER
CREATE/MODIFY CONFIGURATION
K
-
3
Select
3.01 K BALCO.
When
NONE
is selected, the STT04 terminal
branches to a
TEMPERATURE DISPLAY UNITS
selection screen. Choose the desired temperature
unit.
For this example select
AUTO SOLUTION.
NOTE:
Other temperature compensation selections
branch to a
TEMPERATURE DISPLAY UNITS
selec-
tion screen.
This screen is unique to the
AUTO SOLUTION
selection of the
TEMP COMP TYPE
. Other
selections go to the temperature display units.
Select
NO
.
If
YES
is selected, enter 5 input and output points.
Values must be between 0 and 100%.
Refer to the
Smart Specific Ion Transmitter Series
TBN580
instruction for description.
Enter a value between 0 and 32. Refer to the
Smart
Specific Ion Transmitter Series TBN580
instruction
for description.
Key
Display
Comments
E N T E R
TEMP COMP INPUT
→
3.01 K BALCO
NONE
E N T E R
TEMP COMP TYPE
MANUAL
AUTO NERNSTIAN
→
AUTO SOLUTION
AUTO PURE H2O
E N T E R
ENTER SOLUTION
CO-EFFICIENT
±
n.nnn pH per
10
°
C (from 25
°
C)
E N T E R
TEMPERATURE
DISPLAY UNITS
→ °
C
°
F
E N T E R
OUTPUT FUNC GEN
→
NO
YES
E N T E R
OUTPUT ACTION:
→
NORMAL
REVERSE
E N T E R
DAMPING:
(0-32 SEC)
_nn.nn