600T & 600T EN PRESSURE TRANSMITTER
CALIBRATION
Q - 23
METER VALUE ADJUSTMENT
Use this function to adjust the four to 20 milliampere output of the field
device using values from an external current meter. This method is
only valid for HART devices.
Use the arrow keys to adjust the 20 mA signal.
Key
Display
Comments
E N T E R
ADJUST TO 20 mA
THEN HIT ENTER
E N T E R
ID TAGNAME
READY
Key
Display
Comments
This operation will cause a change in output not cor-
responding to the input. Be sure the control loop is in
manual.
Select
YES
.
Select
D-TO-A ADJUST
.
Select
METER VALUE ENTRY
.
C A LI-
B R AT E
E N T E R
OUTPUT WILL BE
AFFECTED! PROCEED?
NO
→
YES
E N T E R
CALIBRATION
SENSOR TRIM
→
D-TO-A ADJUST
PV BIAS
SET OUTPUT %
E N T E R
D/A CAL USING
UPDOWN ARROW
KEYS
→
METER VALUE ENTRY