
PTH PRESSURE TRANSMITTER
CREATE/MODIFY CONFIGURATION
D
-
3
Enter a day and press
. Enter a month and
press
. Enter a year and press
.
This date can represent the creation date of the con-
figuration, the date the device or element was
installed, or some other significant date.
Select
LINEAR
.
In this example
FUNC GENERATOR
is chosen as an
output. Specify five input and output points as a per-
centage of input. The first and last points on the
curve are fixed at 0.00% and 100.00%. The 5 points
are to be between these values.
NOTE:
Other output type selections not shown here
include
LINEAR
,
SQUARE ROOT
,
VOL./ SPHERE
and
VOL./CYLINDER.
Use
to return to a previous configuration
screen from any screen in the configuration process.
Select an output action.
Enter a value between 0 and 32 seconds.
Select an engineering unit best suited for the
application.
Input lower range value using the arrow keys, then
press
. Input the upper range value.
Key
Display
Comments
E N T E R
E N T E R
DATE:
DAY: nn
MONTH: nn
YEAR: nn
ENTER
ENTER
ENTER
E N T E R
OUTPUT TYPE
→
LINEAR
SQUARE ROOT
3/2 FLOW MODE
BACK
E N T E R
OUTPUT ACTION:
→
NORMAL
REVERSE
E N T E R
DAMPING:
(0 - 32 SEC)
_ n.nn SECS
E N T E R
ENGINEERING UNIT
→
iH20
mmH2O
mmHg
PSI
BARS
mBAR
Kgcm
2
KPA
E N T E R
LOWER RANGE VAL
nn.nn UNITS
UPPER RANGE VAL
nn.nn UNITS
ENTER