ADDENDUM
12
STATIC TRIM
Use this option if the instrument is to be statically calibrated using a known pressure.
Key
Display
Comments
This operation will cause a change in output not cor-
responding to the input. Be sure the control loop is in
manual.
Select YES.
Select SENSOR TRIM, or select calibration option
with down-arrow key and refer to the appropriate
section. Press
when done.
Select STATIC TRIM.
Display shows the value of the pressure measured
by the 600T EN transmitter.
Enter the value of the actual static pressure using the
number keys.
C A LI-
B R AT E
E N T E R
OUTPUT WILL BE
AFFECTED! PROCEED?
NO
→
YES
E N T E R
→
SENSOR TRIM
D-TO-A ADJUST
PV BIAS
SET OUTPUT %
ENTER
[ 3 TIMES ]
E N T E R
FULL TRIM
ZERO TRIM
FACTORY TRIM
→
STATIC TRIM
E N T E R
STATIC PRESSURE
value units
PRESS ENTER
TO MODIFY
E N T E R
STATIC PRESSURE
value units
E N T E R
ID TAGNAME
READY