EQS TEMPERATURE TRANSMITTER
CREATE/MODIFY CONFIGURATION
C - 2
Key
Display
Comments
Select
NEW
to create a new configuration.
To modify
an existing configuration, select
MODIFY.
The
screen sequence is the same, however, the
MODIFY
screens will appear with the values and cursor posi-
tions as originally configured.
Select
ABB FSK
.
Use the right arrow key to select
EQS
.
Enter a name for the configuration ID tag using up to
14 ASCII characters. To select a character, press the
key that has the desired character. Continue to press
the key until the desired character appears. Use the
right arrow key to move to the next character. Use the
left arrow key to go back to the previous character.
For this example select
ANALOG.
For this example select
T/C.
Select
N
type.
Choose the desired temperature unit.
C O N F IG
CONFIGURATION
→
NEW
MODIFY
ERASE
E N T E R
DEVICE TYPE
→
ABB FSK
HART
E N T E R
TRANSMITTER TYPE
PTS
→
EQS
BCN
EQN
AVS
TB480 cond
E N T E R
STT04 CONFIGURATION
[
]
←
PREVIOUS
NEXT
→
E N T E R
SELECT MODE:
→
ANALOG
DIGITAL
E N T E R
SENSOR TYPE:
→
T/C
RTD
mV
OHMS
E N T E R
THERMOCOUPLE
→
N
B
E
J
K
R
S
T
C
E N T E R
ENGINEERING UNIT
→
o
C
o
F
o
K