VALUES OUT OF
ACCEPTABLE RANGE
FOR FIELD DEVICE
All FSK Value specified in the con-
figuration is below the
limit.
Refer to the appropriate product instruc-
tion for the value limits.
Check 4 to 20 mA input.
VALVE STUCK
Positioner Valve has not moved for
over two minutes.
Check valve.
Check 4 to 20 mA input.
OPTION NOT
INSTALLED
XM/SM/
XE
The current configuration
is calling to use the empty
pipe detector which
requires an optional
board.
Add empty pipe detector option, or turn
empty pipe detection off in the
configuration.
Table 5-2. STT04 Error Messages for ABB FSK Devices
(continued)
Message
Affected
Device
Probable Cause
Corrective Action