BCN PRESSURE TRANSMITTER
CREATE/MODIFY CONFIGURATION
G - 2
Key
Display
Comments
Select NEW to create a new configuration. To modify
an existing configuration, select MODIFY. The screen
sequence is the same, however, the MODIFY
screens will appear with the values and cursor posi-
tions as originally configured.
Select ABB FSK as device type.
Use the down arrow key and select BCN.
Enter a name for the configuration ID tag using up to
14 ASCII characters. To select a character, press the
key that has the desired character. Continue to press
the key until the desired character appears. Use the
right arrow key to move to the next character. Use the
left arrow key to go back to the previous character.
Select DIGITAL (device in this mode defaults to
below 4 mA, independent of input). Use the up and
down arrow keys to select mode.
NOTE: The DIGITAL selection should only be made
when using an IMFBS01 field bus I/O module. Select
ANALOG for all other cases.
If ANALOG is selected, ENTER CHANNEL # screen
will not appear. The next screen will be TRANSMIT-
TER TYPE. This screen is used to assign an address
to the transmitter for use with the field bus. The
address range is 1 through 8.
C O N F IG
CONFIGURATION
→
NEW
MODIFY
ERASE
E N T E R
DEVICE TYPE
→
ABB FSK
HART
E N T E R
TRANSMITTER TYPE
PTS
EQS
→
BCN
EQN
AVS
TBN480 cond
E N T E R
STT04 CONFIGURATION
[
]
←
PREVIOUS
NEXT
→
E N T E R
SELECT MODE:
ANALOG
→
DIGITAL
E N T E R
ENTER CHANNEL #:
nn