AS800 PRESSURE TRANSMITTER
CALIBRATION
P - 10
Temperature Calibration
Apply zero value to the transmitter.
ZERO TRIM
is complete.
Key
Display
Comments
E N T E R
APPLY 0 INPUT
TO SENSOR
THEN HIT ENTER
E N T E R
ID TAGNAME
READY
Key
Display
Comments
This operation will cause a change in output not cor-
responding to the input. Be sure the control loop is in
manual.
Select
YES
.
Select
TEMP. CAL
.
If digitally configured, the
D-TO-A ADJUST
selection
will not appear.
Enter TEMPERATURE value,
.
C A LI-
B R AT E
OUTPUT WILL BE
AFFECTED! PROCEED?
NO
→
YES
E N T E R
INPUT A/D CAL
D-TO-A ADJUST
ZERO TRIM
→
TEMP. CAL
E N T E R
ENTER SENSOR
TEMPERATURE
ENTER