4.10 Inspecting the bolted joints, etc.
•
Check using a 6 mm diameter rod, that the arm’s alignment check hole is
aligned with the predrilled hole in the mechanism housing.
•
Check that all bolted joints are tightened to the correct torque in accordance
with the table below.
Bolted joint
Tightening torque (Nm)
Frame
430
Foundation
300-350 or 500-550
Operating mechanism
79
Protective tube
79
Circuit-breaker pole
300
Pull-rod
300
Density monitor
10
Bottom cover
22,5
Plates
22,5
Cover
9