Contact and puffer replacement
Overhaul Instructions
18
1HSB435409-201 enrev1
6.2 Inspection of the puffer
Move the contact springs upwards from position a to b. Lift off the puffer and check
that the sliding surfaces on the pull-rod are not worn.
Check that the nozzle is not punctured. Also check that the contact surfaces on the
puffer cylinder are not burnt or worn so that copper is visible.
Replace the entire puffer if it has burnt or worn surfaces or if the nozzle has been
punctured.
Figure 6-2. Puffer
Item
1
Nozzle
2
Pull-rod
3
Puffer cylinder
4
Bolt M8x16
5
Contact springs
1
2
Contact surface
3
B10061
4
5
Contact surface
b
a
TIGHTENING TORQUE
22.5 Nm