Ripple in the DC auxiliary voltage
Max 12% of the DC value (at
frequency of 100 Hz)
Interruption time in the auxiliary DC voltage without
resetting the relay
<50 ms at U
aux
rated
Time to trip from switching on the auxiliary voltage
<350 ms
Internal over temperature limit
+100°C
Fuse type
T2A/250 V
Table 5.2.4.-3
Energizing inputs
Rated frequency
50/60 Hz
±
5 Hz
Rated current, I
n
(CT)
0.2 A
1 A
5 A
Thermal withstand capability:
*
continuously
1.5 A
4 A
20 A
*
for 1 s
20 A
100 A 500 A
*
for 10 s
5 A
25 A
100 A
Dynamic current withstand:
*
half-wave value
50 A
250 A 1250
A
Input impedance
<750
m
Ω
<100
m
Ω
<20
m
Ω
Table 5.2.4.-4
Measuring range
Measured currents on phases I
a
, I
b
and I
c
as
multiples of the rated currents of the energizing
inputs
0...50
×
I
n
(CT)
Ground-fault current as a multiple of the rated
current of the energizing input
0...20
×
I
n
(CT)
Table 5.2.4.-5
Digital inputs
Rated voltage:
DI1...DI2
DI3...DI5 (optional)
REF610CxxHxxx
110/125/220/250 V DC
Activating threshold
Max. 88 V DC (110 V DC -
20%)
REF610CxxLxxx
24/48/60/110/125/
220/250 V DC
Activating threshold
Max. 19,2 V DC (24 V DC -
20%)
REF610CxxxxLx
24/48/60/110/125/
220/250 V DC
Activating threshold
Max. 19,2 V DC (24 V DC -20%)
REF610CxxxxHx
110/125/220/250 V DC
Activating threshold
Max. 88 V DC (110 V DC -20%)
Operating range
±
20% of the rated voltage
Current drain
2...18 mA
Power consumption/input
≤
0.9 W
152
REF610
REF610
Feeder Protection Relay
Technical Reference Manual - ANSI Version