Table 5.1.15.1.-15
Event record
Address
Signal name
Range
Comment
671
Latest selection code
a)
1...3
1 = read oldest unread record
2 = read oldest stored record
3 = clear Modbus event buffer
-1...-99
-1...-99 = move to the nth
newest record
672
Sequence number
1...255
673
Unread records left
0...99
674
Time stamp of the event, date
2 bytes: YY.MM
675
Time stamp of the event, date and time
2 bytes: DD.HH
676
Time stamp of the event, time
2 bytes: MM.SS
677
Time stamp of the event, time
0...999
0...999 ms
678
Modbus DI point or informative event (SPA channel)
0/1
*
DI event
0
When MSB = 0, bits 14...0
indicate the DI point.
*
Informative event
1
When MSB = 1, bits 14...0
indicate the SPA channel.
679
DI value or SPA event code
*
DI event
0/1
In case of a DI event, the
register will contain the DI
value.
*
Informative event
0...63
In case of an informative event,
the register will contain the
SPA event code.
a)
Readable and writeable register.
Structure 4
The relay's real-time clock is stored in this structure. It can be updated by presetting
the whole register structure in one Modbus transaction.
Table 5.1.15.1.-16
Real-time clock structure
Address
Description
Range
721
Year
0...99
722
Month
1...12
723
Day
1...31
724
Hour
0...23
725
Minute
0...59
726
Second
0...59
727
Hundredth of a second
0...99
5.1.16.
DNP 3.0 remote communication protocol
The DNP 3.0 protocol was developed by Harris Control based on the early versions
of the IEC 60870-5 standard telecontrol protocol specifications. Today, the DNP
protocol specifications are controlled by the DNP Users Group.
102
REF610
REF610
Feeder Protection Relay
Technical Reference Manual - ANSI Version