119
Recorded data
Parameter
V1
shows the element and phase which caused the trip. Parameter
V2
shows the trip target code.
Parameters
V3
...
V8
show the number of pickups of the protection elements,
parameters
V9
...
V12
the number of trips of the protection elements , and parameters
V13...V24 the number of initiated auto-reclose shots.
Table 5.1.17.-3
Recorded data: Channel 0
Recorded data
Parameter (R)
Value
Element/phase
which caused the
trip
V1
1=I
c
(51P)
2=l
b
(51P)
4=l
a
(51P)
8=51N
16=l
c
(50P-1)
32=l
b
(50P-1)
64=l
a
(50P-1)
128=50N
256=l
c
(50P-2)
512==l
b
(50P-2)
1024=l
a
(50P-2)
2048=46
4096=49
8192=external trip
16384=AR
32768=trip of element ARC (local)
65536=trip of element ARC (remote)
Trip target code
V2
0 =
—
1=pickup of element 51P
2=trip of element 51P
3=pickup of element 50P-1
4=trip of element 50P-1
5=pickup of element 50P-2
6=trip of element 50P-2
7=pickup of element 51N
8=trip of element 51N
9=pickup of element 50P-1
10=trip of element 50P-1
11=pickup of element 46
12=trip of element 46
13=alarm of element 49
14=trip of element 49
15=external trip
16=definite trip alarm
17=CB reclosing failed
Feeder Protection Relay
Technical Reference Manual - ANSI Version
REF610
REF610