Variable
Group/
Channel
1 (R, W,
P)
Setting
range
Default
setting
Custo-
mer
’
s
setting
Checksum, SGF 2
1S62
0...127
0
Checksum, SGF 3
1S63
0...127
120
Checksum, SGF 4
1S64
0...63
0
Checksum, SGF 5
1S65
0...255
0
Checksum, SGB 1
1S71
0...1048575
0
Checksum, SGB 2
1S72
0...1048575
0
Checksum, SGB 3
1S73
0...1048575
0
Checksum, SGB 4
1S74
0...1048575
0
Checksum, SGB 5
1S75
0...1048575
0
Checksum, SGR 1
1S81
0...8388607
2108074
Checksum, SGR 2
1S82
0...8388607
2108074
Checksum, SGR 3
1S83
0...8388607
2108074
Checksum, SGR 4
1S84
0...8388607
5461
Checksum, SGR 5
1S85
0...8388607
5461
Checksum, SGR 6
1S86
0...8388607
0
Checksum, SGR 7
1S87
0...8388607
0
Checksum, SGR 8
1S88
0...8388607
0
Checksum, SGL 1
1S91
0...8388607
0
Checksum, SGL 2
1S92
0...8388607
0
Checksum, SGL 3
1S93
0...8388607
0
Checksum, SGL 4
1S94
0...8388607
0
Checksum, SGL 5
1S95
0...8388607
0
Checksum, SGL 6
1S96
0...8388607
0
Checksum, SGL 7
1S97
0...8388607
0
Checksum, SGL 8
1S98
0...8388607
0
Table 8.-2
Setting group 2
Variable
Group/
Channel 2
(R, W, P)
Setting range
Default
setting
Custo-
mer
’
s
setting
Pickup value of element 51P
2S1
0.30...5.0 x I
n
(CT)
0.30 x I
n
(CT)
Operate time of element 51P (51P
TDLY)
2S2
0.05...300 s
0.05 s
Time/current characteristic for
element 51P
2S3
0...9
0
Time multiplier 51P TD IEC
2S4
0.05...1.00
0.05
Time multiplier 51P TD ANSI
2S5
1.0...15.0
1.0
Resetting time of element 51P
(51P RSET)
2S6
0.05...2.50 s
0.05 s
Pickup value of element 50P-1
2S7
0.50...35.0 x I
n
(CT)
0.50 x I
n
(CT)
Operate time of element 50P-1
(50P-1 TDLY)
2S8
0.04...300 s
0.04 s
168
REF610
REF610
Feeder Protection Relay
Technical Reference Manual - ANSI Version
1MRS755535
Summary of Contents for RELION REF610
Page 1: ...Feeder Protection Relay REF610 REF610 Technical Reference Manual ANSI Version ...
Page 2: ......
Page 6: ...6 ...
Page 8: ...8 ...
Page 12: ...12 ...
Page 14: ...14 ...
Page 20: ...20 ...
Page 164: ...164 ...
Page 175: ......