Feature
Value
Operation accuracy
*
10...100%
±3% of the set pickup value and ±1 unit
Table 5.1.4.11.-5
Element ARC and L>
Feature
Value
Element ARC
Set trip value ArcI>
0.5...35.0 x I
n
(CT)
Operate time
< 15 ms
a)
ArcI
0
>
5.0...800% I
n
(CT)
Operate time
< 17 ms
a)
Resetting time
30 ms
Operation accuracy
±7% of the set pickup value
L>
Activation time of L>
< 15 ms
Resetting time
20 ms
a)
Applies only if a non-trip output contact (SO1...5) is used. If a trip output contact (PO1...3) is used, 2...3
ms will be added.
Fig. 5.1.4.11.-1
Relative sensitivity of lens sensors
72
REF610
REF610
Feeder Protection Relay
Technical Reference Manual - ANSI Version
1MRS755535