Variable
Actual settings
(R), channel 0
Group/Channel 1
(R, W, P)
Group/Channel 2
(R, W, P)
Setting range
Checksum, SGB 2
S72
1S72
2S72
0...1048575
Checksum, SGB 3
S73
c)
1S73
2S73
0...1048575
Checksum, SGB 4
S74
c)
1S74
2S74
0...1048575
Checksum, SGB 5
S75
c)
1S75
2S75
0...1048575
Checksum, SGR 1
S81
1S81
2S81
0...8388607
Checksum, SGR 2
S82
1S82
2S82
0...8388607
Checksum, SGR 3
S83
1S83
2S83
0...8388607
Checksum, SGR 4
S84
1S84
2S84
0...8388607
Checksum, SGR 5
S85
1S85
2S85
0...8388607
Checksum, SGR 6
S86
c)
1S86
2S86
0...8388607
Checksum, SGR 7
S87
c)
1S87
2S87
0...8388607
Checksum, SGR 8
S88
c)
1S88
2S88
0...8388607
Checksum, SGL 1
S91
1S91
2S91
0...8388607
Checksum, SGL 2
S92
1S92
2S92
0...8388607
Checksum, SGL 3
S93
1S93
2S93
0...8388607
Checksum, SGL 4
S94
1S94
2S94
0...8388607
Checksum, SGL 5
S95
1S95
2S95
0...8388607
Checksum, SGL 6
S96
1S96
2S96
0...8388607
Checksum, SGL 7
S97
1S97
2S97
0...8388607
Checksum, SGL 8
S98
1S98
2S98
0...8388607
a)
If the protection element is out of operation, the number indicating the currently used value will be displaced by
“
999
”
when the parameter is
read via the SPA bus and by dashes on the LCD.
b)
If the optional/O module has not been installed, a dash will be shown on the LCD and
“
999
”
when the parameter is read via the SPA bus.
c)
If the optional/O module has not been installed, a dash will be shown on the LCD and
“
9999999
”
when the parameter is read via the SPA bus.
Auto-reclose parameters
Table 5.1.17.-2
Auto-reclose parameters
Description
Parameter (R,
W, P), channel
0
Value
CB Closing time
V121
0.1...10 s
Start delay of element 51P
V122
0...300 s
Start delay of element 51N
V123
0...300 s
Reclaim time
V124
3...300 s
Cutout time
V125
0.1...300 s
Dead time of shot 1
V126
0.1...300 s
Dead time of shot 2
V127
0.1...300 s
Dead time of shot 3
V128
0.1...300 s
SG1
V129
0...255
SG2
V130
0...1023
SG3
V131
0...31
The AR function can be activated either via the or with SPA parameter
S25
by
setting the number of auto-reclose shots to 1, 2 or 3.
118
REF610
REF610
Feeder Protection Relay
Technical Reference Manual - ANSI Version
1MRS755535
Summary of Contents for RELION REF610
Page 1: ...Feeder Protection Relay REF610 REF610 Technical Reference Manual ANSI Version ...
Page 2: ......
Page 6: ...6 ...
Page 8: ...8 ...
Page 12: ...12 ...
Page 14: ...14 ...
Page 20: ...20 ...
Page 164: ...164 ...
Page 175: ......