Table 5.1.17.1.-7
Event codes E25...E42
Channel
Event
Description
Weighting
factor
Default
value
1
E25
Pickup signal from element 49 activated
1
0
1
E26
Pickup signal from element 49 reset
2
0
1
E27
Alarm signal from element 49 activated
4
1
1
E28
Alarm signal from element 49 reset
8
0
1
E29
Trip signal from element 49 activated
16
1
1
E30
Trip signal from element 49 reset
32
0
1
E31
Trip signal from element ARC (light and
current) activated
64
1
1
E32
Trip signal from element ARC (light and
current) reset
128
0
1
E33
Trip signal from element ARC (DI and
current) activated
256
0
1
E34
Trip signal from element ARC (DI and
current) reset
512
0
1
E35
Light signal output activated
1024
0
1
E36
Light signal output reset
2048
0
1
E37
Trip lockout signal activated
4096
1
1
E38
Trip lockout signal reset
8192
0
1
E39
External trip signal activated
16384
0
1
E40
External trip signal reset
32768
0
1
E41
CBFAIL activated
65536
0
1
E42
CBFAIL reset
131072
0
Default value of event mask 1V157
4180
Channel 2
Table 5.1.17.1.-8
Event codes E1...E16
Channel
Event
Description
Weighting
factor
Default
value
2
E1
PO1 activated
1
1
2
E2
PO1 reset
2
1
2
E3
PO2 activated
4
0
2
E4
PO2 reset
8
0
2
E5
PO3 activated
16
0
2
E6
PO3 reset
32
0
2
E7
SO1 activated
64
0
2
E8
SO1 reset
128
0
2
E9
SO2 activated
256
0
2
E10
SO2 reset
512
0
2
E11
SO3 activated
1024
0
2
E12
SO3 reset
2048
0
2
E13
SO4 activated
4096
0
2
E14
SO4 reset
8192
0
134
REF610
REF610
Feeder Protection Relay
Technical Reference Manual - ANSI Version
1MRS755535
Summary of Contents for RELION REF610
Page 1: ...Feeder Protection Relay REF610 REF610 Technical Reference Manual ANSI Version ...
Page 2: ......
Page 6: ...6 ...
Page 8: ...8 ...
Page 12: ...12 ...
Page 14: ...14 ...
Page 20: ...20 ...
Page 164: ...164 ...
Page 175: ......