67
Switch
Function
Default setting
SGL1...8/23
Disturbance recorder triggered
0
Σ
SGL1...SGL8
0
Auto-reclose SG1...SG3
Switchgroup SG1 is used for blocking the initiation of one or several auto-reclose
shots, SG2 for blocking of protection elements at one or several auto-reclose shots,
and SG3 for disabling the AR function as follows:
Table 5.1.4.10.-10
SG1
Switch
Function
Default setting
SG1/1
Blocking of initiation of shot 1 by the trip signal from element 50P-1
0
SG1/2
Blocking of initiation of shot 1 by the external AR initiation signal
0
SG1/3
Blocking of initiation of shot 1 by the trip or delayed pickup signal from element
51P
0
SG1/4
Blocking of initiation of shot 1 by the trip or delayed pickup signal from element
51N or the trip signal from element 50N
0
SG1/5
Blocking of initiation of shot 2 and 3 by the trip signal from element 50P-1
0
SG1/6
Blocking of initiation of shot 2 and 3 by the external AR initiation signal
0
SG1/7
Blocking of initiation of shot 2 and 3 by the trip or delayed pickup signal from
element 51P
0
SG1/8
Blocking of initiation of shot 2 and 3 by the trip or delayed pickup signal from
element 51N or the trip signal from element 50N
0
*
When the switch is in position 1, shot initiation is blocked.
Σ
SG1
0
Table 5.1.4.10.-11
SG2
Switch
Function
a)
Default setting
SG2/1
Blocking of tripping of element 51P at shot 1
0
SG2/2
Blocking of tripping of element 50P-1 at shot 1
0
SG2/3
Blocking of tripping of element 50P-2 at shot 1
0
SG2/4
Blocking of tripping of element 51N at shot 1
0
SG2/5
Blocking of tripping of element 50N at shot 1
0
SG2/6
Blocking of tripping of element 51P at shots 2 and 3
0
SG2/7
Blocking of tripping of element 50P-1 at shots 2 and 3
0
SG2/8
Blocking of tripping of element 50P-2 at shots 2 and 3
0
SG2/9
Blocking of tripping of element 51N at shots 2 and 3
0
SG2/10
Blocking of tripping of element 50N at shots 2 and 3
0
*
When the switch is in position 1, the element is blocked.
0
Σ
SG2
0
a)
The blocking is active until the set cutout time or the set reclaim time elapses or the AR function is locked out.
Feeder Protection Relay
Technical Reference Manual - ANSI Version
REF610
REF610
1MRS755535