85
Table 5.1.14.-1
Information mapping of configuration set 1 and 2
Event reason
Event
code
Configuration
set
1
Configuration
set
2
Function
type
Information
number
GI
Relative
time
T
ype
identification
Disturbance recorder Triggered/Cleared
0E31/
0E32
X
X
178
100
-
-
1
HMI Setting password Opened/Closed
0E33/
0E34
X
X
178
101
-
-
1
HMI Communication password Opened/Closed
0E35/
0E36
X
X
178
102
-
-
1
51P Pickup/Reset
1E1/
1E2
X
X
160
84
X
1E1
2
51P Trip/Reset
1E3/
1E4
X
X
160
90
-
1E1
2
50P-1 Pickup/Reset
1E5/
1E6
X
X
162
94
X
1E5
2
50P-1 Trip/Reset
1E7/
1E8
X
X
160
91
-
1E5
2
50P-2 Pickup/Reset
1E9/
1E10
X
X
162
96
X
1E9
2
50P-2 Trip/Reset
1E11/
1E12
X
X
162
98
-
1E9
2
51N Pickup/Reset
1E13/
1E14
X
X
160
67
X
1E13
2
51N Trip/Reset
1E15/
1E16
X
X
160
92
-
1E13
2
50N Pickup/Reset
1E17/
1E18
X
X
162
95
X
1E17
2
50N Trip/Reset
1E19/
1E20
X
X
160
93
-
1E17
2
46 Pickup/Reset
1E21/
1E22
X
X
173
84
X
1E21
2
46 Trip/Reset
1E23/
1E24
X
X
173
90
-
1E21
2
49 Pickup/Reset
1E25/
1E26
X
X
184
84
X
1E25
2
49 Alarm/Reset
1E27/
1E28
X
X
184
11
X
-
1
49 Trip/Reset
1E29/
1E30
X
X
184
90
-
1E25
2
ARC (light and current) Trip/Reset
1E31/
1E32
X
X
100
90
-
1E31
2
ARC (DI and current) Trip/Reset
1E33/
1E34
X
X
100
50
-
1E33
2
Arc light signal output Activated/Reset
1E35/
1E36
X
X
100
20
-
-
1
Feeder Protection Relay
Technical Reference Manual - ANSI Version
REF610
REF610
1MRS755535
Summary of Contents for RELION REF610
Page 1: ...Feeder Protection Relay REF610 REF610 Technical Reference Manual ANSI Version ...
Page 2: ......
Page 6: ...6 ...
Page 8: ...8 ...
Page 12: ...12 ...
Page 14: ...14 ...
Page 20: ...20 ...
Page 164: ...164 ...
Page 175: ......