155
REF610CxxLxxx and REF610CxxxxLx
Class B
*
Common mode
300 V rms
*
Differential mode
100 V rms
Voltage dips and short interruptions
According to IEC 61000-4-11
30%/10 ms
60%/100 ms
60%/1000 ms
>95%/5000 ms
Electromagnetic emission tests
According to the EN 55011
*
Conducted, RF-emission (Mains terminal)
EN 55011, class A, IEC 60255-25
*
Radiated RF-emission
EN 55011, class A, IEC 60255-25
CE approval
Complies with the EMC directive EMC 2004/
108/EC and the LV directive LV 2006/95/EC
Table 5.2.4.-13
Standard tests
Insulation tests:
Dielectric tests
According to IEC 60255-5
*
Test voltage
2 kV, 50 Hz, 1 min
Impulse voltage test
According to IEC 60255-5
*
Test voltage
5 kV, unipolar impulses, waveform
1.2/50
μ
s, source energy 0.5 J
Insulation resistance measurements
According to IEC 60255-5
*
Isolation resistance
>100 M
Ω
, 500 V DC
Mechanical tests:
Vibration tests (sinusoidal)
According to IEC 60255-21-1, class I
Shock and bump test
According to IEC 60255-21-2, class I
Table 5.2.4.-14
Data communication
Rear interface:
*
Fibre-optic or RS-485 connection
*
SPA bus, IEC 60870-5-103, DNP 3.0 or Modbus protocol
*
9.6 or 4.8 kbps (additionally 2.4, 1.2 or 0.3 kbps for Modbus)
Front interface:
*
Optical connection (infrared): wirelessly or via the front communication cable
(1MRS050698)
*
SPA bus protocol
*
9.6 or 4.8 kbps (9.6 kbps with front communication cable)
Optional communication modules and protocols
*
SPA-bus, IEC 60870-5-103, Modbus® (RTU and ASCII):
*
Plastic fibre
*
Plastic fibre with arc protection input
*
Plastic and glass fibre
*
Plastic and glass fibre with arc protection input
*
RS485
*
RS485 with arc protection input
*
DNP 3.0:
Feeder Protection Relay
Technical Reference Manual - ANSI Version
REF610
REF610
1MRS755535
Summary of Contents for RELION REF610
Page 1: ...Feeder Protection Relay REF610 REF610 Technical Reference Manual ANSI Version ...
Page 2: ......
Page 6: ...6 ...
Page 8: ...8 ...
Page 12: ...12 ...
Page 14: ...14 ...
Page 20: ...20 ...
Page 164: ...164 ...
Page 175: ......