It shall be noted that depending on national standard and utility practices, the rated
secondary current of a CT has typically one of the following values:
•
1A
•
5A
However, in some cases, the following rated secondary currents are used as well:
•
2A
•
10A
The IED fully supports all of these rated secondary values.
It is recommended to:
•
use 1A rated CT input into the IED in order to connect CTs with
1A and 2A secondary rating
•
use 5A rated CT input into the IED in order to connect CTs with
5A and 10A secondary rating
4.2.2.5
Example on how to connect a wye connected three-phase CT set to the
IED
SEMOD55055-352 v11
gives an example about the wiring of a wye connected two-phase CT set to
the IED. It gives an overview of the actions which are needed to make this
measurement available to the built-in protection and control functions within the IED
as well.
For correct terminal designations, see the connection diagrams valid for
the delivered IED.
Section 4
1MRK 505 370-UUS A
Analog inputs
74
Busbar protection REB670 2.2 ANSI
Application manual
Summary of Contents for RELION REB670
Page 1: ...RELION 670 SERIES Busbar protection REB670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 24: ...18 ...
Page 40: ...34 ...
Page 72: ...66 ...
Page 102: ...96 ...
Page 266: ...260 ...
Page 272: ...266 ...
Page 290: ...284 ...
Page 432: ...426 ...
Page 542: ...536 ...
Page 552: ...546 ...
Page 553: ...547 ...