100
30
5
IMagComp5
IMagComp30
IMagComp100
-10
+10
Magnitude
compensation
% of In
Measured
current
% of In
0-5%:
Constant
5-30-100%: Linear
>100%:
Constant
100
30
5
IAngComp5
IAngComp30
IAngComp100
-10
+10
Angle
compensation
Degrees
Measured
current
% of In
ANSI05000652_3_en.vsd
ANSI05000652 V3 EN-US
Figure 189:
Calibration curves
14.1.4.1
Setting examples
SEMOD54481-4 v5
Three setting examples, in connection to Measurement function (CVMMXN), are
provided:
•
Measurement function (CVMMXN) application for a OHL
•
Measurement function (CVMMXN) application on the secondary side of a
transformer
•
Measurement function (CVMMXN) application for a generator
For each of them detail explanation and final list of selected setting parameters values
will be provided.
The available measured values of an IED are depending on the actual
hardware (TRM) and the logic configuration made in PCM600.
1MRK 505 370-UUS A
Section 14
Monitoring
Busbar protection REB670 2.2 ANSI
433
Application manual